If the BAH solution with brine pre-heating is selected:
↳ Frost protection
↳ Frost protection heat exchanger
↳ BAH minimum temperature (ºC)
↳ BAH maximum temperature (°C)
↳ BAH regulatory deadband (°C)
De-icing the heat exchanger:
↳ De-icing heat exchanger
↳ Frost protection below temp. (°C)
↳ Maximum time de-icing (min)
↳ Minimum time between de-icing
(min)
↳ Extract air fan during de-icing
↳ Supply air fan during de-icing
Compact P / Compact P Polar (English)
Setting:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
BAH
-10 ↔ 10°C
5°C
At an outdoor temperature below the minimum
temperature, the circulation pump in the BAH solution
starts up as a safeguard against icing in the
counterflow heat exchanger.
15 ↔ 35°C
25°C
At an outdoor temperature above the maximum
temperature, the circulation pump in the BAH solution
starts up in order to cool the outdoor air and prevent
the dwelling from warming up.
(At a temperature between the minimum and
maximum temperatures, the circulation pump will be
inactive).
0 ↔ 10.0°C
2.0°C
The regulatory deadband for temperature regulation.
-10 ↔ 1°C
1°C
Indicates when the control system is to start
monitoring of the heat exchanger via the T4
temperature sensor after the heat exchanger.
10 ↔ 90 minutes
25 minutes
Indicates how long the unit needs to perform the de-
icing function for the heat exchanger.
15 ↔ 180 minutes
30 minutes
Indicates the minimum time between de-icing the heat
exchanger.
Level 1 / Level 2 / Level 3 / Level 4
Level 2
Indicates the speed level at which the extract air fan is
to run during de-icing of the heat exchanger.
Normal / Extract air
Extract air
Indicates how the supply air fan is to run during de-
icing:
Normal: The supply air fan continues running at the set
level.
Extract air: The supply air fan runs at the same level as
the extract air fan.