Temperature regulation
↳ Master sensor indoor room
temperature
↳ Temperature regulatory deadband (°C) Settings:
↳ Temperature offset bypass (°C)
External heating regulation
↳ Deadband external room heating (°C)
Regulation of external heat source
20°C
Room temperature ˂ 18°C releases external heat supply
Compact P / Compact P Polar (English)
Settings:
Standard setting:
Description:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Settings:
Standard setting:
Description:
Regulatory deadband for external heating (ºC)
Permanent setting 1°C
Room temperature ˂ 19°C blocks external heat supply
T3 / TExt
T3
Here it is selected which temperature sensor is used
for measuring the room temperature.
T3 the temperature sensor in the extract air.
TExt external temperature sensor located in the
dwelling (not a Nilan supply).
0 ↔ 10°C
1°C
Here the regulatory deadband is set for temperature
regulation.
0 ↔ 10°C
0°C
Here is set when the bypass damper is to open,
thereby diverting the air past the heat exchanger.
(Room temperature setpoint + Regulatory deadband +
Offset bypass damper)
The bypass damper only opens if the outdoor
temperature is lower than the indoor temperature
0 ↔ 10°C
1°C
The unit can control an external heat supply by sending
a release or blocking signal. The regulatory deadband
for the control system is set here.
BY NILAN
23