Sensors
Sensor Adjustments
Adjusting the "Lights Not On" Level
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
1. Place timer in Test Mode (see page 8).
2. Set photo cell to maximum. Turn the blue knob full
clockwise (lights on no matter how bright the natural
light is), then about 30° counterclockwise.
3. Check for Lights-Out. Move from underneath the
sensor, and remain still until the lights turn off. Move
around normally to turn the light on.
4. Adjust to desired level. If lights remain off, adjust the
blue knob another 30° counterclockwise and repeat
step 3 until the lights turn on.
NOTE: Set blue knob to 100% to disable photo cell
functionality and leave secondary dry contact closure
output functionality intact.
S p e c i f i c at i o n S u b m i t ta l
®
Job Name:
Job Number:
LOS-CDT Series
(continued)
Model Numbers:
Control Settings (Blue Knob)
LOS-CDT-500R-WH, LOS-CDT-1000R-WH, and LOS-CDT-2000R-WH only
Minimum (low):
Lights will never come on, even though
room is occupied.
0
1000
Maximum (high):
Photo cell has no effect on operation
(factory setting).
0
1000
Normal:
200 lx to 600 lx is normal range.
0
1000