Filter Wiring And Installation; Wiring - Mitsubishi Electric MELSERVO EMC Installation Manuallines

Ac servo system
Hide thumbs Also See for MELSERVO EMC:
Table of Contents

Advertisement

3.3

Filter wiring and installation

When connecting multiple servo amplifiers to one EMC filter, refer to the following.
Page 32 Connecting multiple servo amplifiers to one EMC filter

Wiring

Wire the servo and filter as shown below.
Molded-
Power
case
supply
circuit
breaker
Separate the EMC filter input cable and output cable as far as possible. If they are too close, the noise generated from the
output cable is induced into the input cable, and the filter is not effective. Separate the cables by at least 30 cm if possible.
3 EMC COUNTERMEASURES
10
3.3 Filter wiring and installation
EMC
Magnetic
filter
contactor
Wiring length 1.5m or less (recommended)
Separate the cables by at least 30 cm.
Output (servo amplifier side)
EMC
filter
Servo amplifier
Main circuit
power supply
Control circuit
power supply
Input (power supply side)
Servo
motor

Advertisement