Serial RJ45 Port with IRIG-B Support
8
Figure 4.12
a
In RS232 mode, the RJ45 ports conform to EIA-561 DTE, which transmit on TXD and receive on RXD.
Note
Pins 7 and 8 are connected internally. In RS232 mode, these pins enter a high
impedance state. A DTE that asserts RTS will see CTS asserted. However, the device
will not perform hardware flow control.
4.5

BNC Ports

The following BNC ports are available on the PTP module:
1
2
3
Figure 4.13
Inputs are controlled by RUGGEDCOM RS416PF and only one can be active at
any time. For information about activating an input, refer to the RUGGEDCOM
RUGGEDCOM RS416PF User Guide for the RUGGEDCOM RS416PF.
The color of the Sync LED on the front panel of the PTP module indicates the status
of the incoming timing signal:
RUGGEDCOM RS416PF
Installation Manual, 04/2021, C79000-G8976-1355-04
Serial RJ45 Port Pin
Configuration
1
2
3
TTL OUT Port
Sync LED
TTL IN Port
PTP Module
Green – Signal locked
Amber/Yellow – Holdover (GPS lock has been achieved, but the receiver no
longer sees the minimum number of required satellites)
 
1
 
Communication Ports
Pin
RS232
RS485
Mode
Mode
1
 
2
+IRIG-B
3
Common (Isolated) Ground
4
Common (Isolated) Ground
a
5
RXD
a
6
TXD
TX/RX+
7
CTS
8
RTS
TX/RX-
Shield
Chassis Ground
Port
TTL OUT
PPS signal output,
software selectable
TTL IN
4.5 BNC Ports
RS422
Mode
 
RX-
 
RX+
TX+
 
 
TX-
Function
IRIG-B PWM or 1
TTL-level IRIG-B
PWM signal input