5.2 Fault Finding
If the measured pressure goes above URV or goes below LRV, the output
signal will saturate at the following values:
fault
indication
←
3.6 mA
2 mA
-2.5%
Figure 5-1: Fault finding from the output signal
Fault indications
If there is a specified fault condition, the transmitter output changes to the
specified NAMUR alarm level. The alarm level is set by the position of
DIP switch 2 (refer to Table 4-1).
If applicable, the optional display shows an alarm code to help identify the fault.
Table 5-1 shows some of the codes. If there are several fault conditions, the
alarm code is the sum of all the applicable codes.
K0297 Issue 2
LRV -
not
under
allowed
range
3.8 mA
4 mA
-1.25%
0.00%
- URV
normal signal range
20 mA
100%
5-2
over
not
range
allowed
20.5 mA
21 mA
103.15%
106.25%
fault
indication
→
22 mA