Technical description
Part no.:
Operation Voltage:
Maximum Power Consumption:
Battery (NiMH):
Battery Protection:
Min./Max. Charge Current:
Charge Voltage Range:
Charging Time:
Emergency Mode Duration:
Lumen output, normal:
Lumen output, emergency (1h/3h/8h):
Produced in accordance with:
Ambient Temperature Range:
Relative Humidity:
Degress of cover protection:
Technical lifetime (light source):
Weight:
Expected Battery Lifetime:
Controlgear classification in accordance with IEC 62034: with automatic test function
Description
Indicator LEDs
Normal
Charging (battery test not possible while charging
Mains off, battery not connected or charger fault
Battery test
Battery fault
Light source test
Light source fault
Battery fault and light source fault
LED Status explanation
Off
On
Manual test functions
Manual tests can only be performed if both mains and battery are connected.
By pressing the test button briefly (less than 5 seconds) an emergency operation test is performed. The exit sign will be lit
for approximately 3 seconds, the red indicator LED will flash during this test sequence.
By pressing the test button for a time space between 5 and 10 seconds, a battery condition test is performed. This test will
last for the stated duration and can only be performed when the battery is fully charged (steady green indicator LED). The
exit sign will be lit and the yellow indicator LED will flash during this test sequence.
Resetting errors
Push the test button for a time space between 10 and 15 seconds to delete all indicated errors. Then the luminaire enters
regular operation mode.
Honeywell Life Safety AS, Po. Box 3514, N-3007 Drammen, Norway
MaxLED 26m
138009
4.2W / 4.4VA
3.6V / 1.2Ah
Overcharge protection / Deep discharge protection
1h / 3h / 8h manually selected (default 1h)
280lm
280/110/40lm
EN 60598-1, EN 60598-2-22, EN 55015
EN 61547, EN 61000-3-2, EN 61000-3-3
1068 gr
The MaxLED is a self-contained LED exit sign with selftest
function.
It can be configured as maintained or non-maintained.
Selftest functions
Every 15 days the luminaire will perform an emergency
operation test. This will light the exit sign for approximately 3
seconds. The red indicator LED will flash during this test
sequence.
Every 6 months the luminaire will perform a battery condition
test. The test will last for the stated duration. The exit sign will be
lit and the yellow indicator LED will flash during this test
sequence.
Note: When using DALI or Wireless communication, the
frequencies and schedules for tests will instead be determined
by the connected PC software.
Flashing
MaxLED 47m
138254
220-240V AC, 50-60 Hz
7.2W / 7.6VA
4.8V / 1.2Ah
40 / 160mA
4 - 6V
16 hours
550lm
425/170/60lm
o
5 to 40 C
Up to 95%
IP40
> 100000 hours
1591 gr
4 years
http://www.hls-nordic.com
GB
MaxLED 65m
138255
9.8W / 10.2VA
900lm
425/170/60lm
2355 gr