3.2

SPECIFICATIONS

Maximum operating pressure (with valve shut
off)
Operating temperature range of fluid
Storage temperature range
Materials used
3.3

NOZZLE COUPLINGS

NH (National Hose Threads) threads are standard on all nozzles. Other threads such as NPSH (National Pipe Straight Hose) may be
specified at time of order.
CAUTION
CAUTION
3.4

USE WITH SALT WATER

Use with salt water is permissible provided the equipment is thoroughly cleaned with fresh water after each use. The service life of the
equipment may be shortened due to the effects of corrosion, and is not covered under warranty.
©Copyright Task Force Tips LLC 2002-2020
Mismatched or damaged waterway connections may cause equipment to leak or uncouple under
pressure. Failure could result in injury. Equipment must be mated to matched connections.
Dissimilar metals coupled together can cause galvanic corrosion that can result in the inability to
uncouple the connection, or complete loss of engagement over time. Failure could cause injury. Per
NFPA 1962, if dissimilar metals are left coupled together, an anti-corrosive lubricant should be
applied to the connection and the coupling should be disconnected and inspected at least
quarterly.
Metro 0 - 580 psi
Metro 1 - 300 psi
Metro 2 - 300 psi
33 to 120° F
-40 to 150° F
Aluminum 6000 series hard anodized MIL8625 class 3 type
2, stainless steel 300 series, nylon 6-6, nitrile rubber
Table 3.2
5
40 bar
21 bar
21 bar
1 to 50° C
-40 to 65° c