General In order to get the ultimate benefit from your EVC 13 we recommend that you read through this Installation and Maintenance Instruction. EVC 13 is intended for houses with water based heating. The electric boiler is installed horizontally, suitably on an electric water heater in a “cabinet model”...
The outside temperature sensor is supplied. The output is connected and disconnected with the help of two contactors and two relays. EVC 13 has an integrated circulation pump, expansion vessel, safety valve, tapping valve, load monitor and an input for centralised load control.
Front panel Offset heating curve Heating curve selection Boiler temperature Switch Clock Night change OF F °C Boiler Fuse Indicator lamps pressure Selector EVC 13...
Page 7
“Selector”. Fuse Fuse (2.5 A) for control and the circulation pump. Selector Selector switch with three positions. Permanent day Night change not active Auto mode. Timer controlled night change. Permanent night Night change permanently active. EVC 13...
Warm weather conditions If the room temperature is low, turn the Offset heat- ing curve knob one step clockwise. If the room temperature is high, turn the Offset heat- ing curve knob one step anticlockwise. EVC 13...
The change is active during the pe- riods set on the clock (see section “Clock” - “Programming the timer”). NOTE! An increase in the room temperature may be inhibited by the radiator or floor heating thermostats, if so these must be turned up. EVC 13...
Heating curve VÄRMEKURVA °C The heating control system on EVC 13 is controlled by the outside temperature. This means that the boiler temperature and with that also the flow temperature is regulated in relation to the current outdoor tempera- ture.
“Night change” selector. The selector pressing the keys, positioned around the timer dis- switches between “Permanent day”, “Permanent play. The numbers around the display represent night” and “Auto mode.”. See the section “Front panel”. the 24 hours in a day. EVC 13...
Tariff control (extra option) so see the section “Commissioning and adjusting” - “Filling”. The external water heater is always fed via EVC 13 ir- respective of external control when the power switch is pressed in so that the red marking is visible.
Low room temperature No hot water Circuit or main MCB tripped. In those cases the EVC 13 feeds an electric hot water heater, no hot water may be due to one of the follow- Tripped control fuse, see the section “Monitoring ing reasons: and maintenance”...
030 65 040 90 Helping the circulation pump to start Shut down EVC 13 by turning the switch (8) to “0”. Loosen the venting screw with a screwdriver. Hold a cloth around the screwdriver blade as a certain Venting screw Luftningsskruv amount of water may run out.
R15 ( " ) hose coupling. The cap on the dry. EVC 13 is designed to be positioned on top of the valve should be dismantled and the hose coupling an electric water heater type NIBE COMPACT. Make...
0.5 (bar). Pressure controlled bypass valve EVC 13 is equipped with a pressure controlled bypass valve (48). This is to protect the circulation pump in in- stallations where the radiator flow can completely stop. When the radiator side is closed, the boiler water circulates across the pump internally in EVC 13.
The boiler is connected on terminal (9) to 400 V 3- phase, neutral + earth via a distribution board with fuses. EVC 13 does not include an isolator switch on the NOTE! incoming electrical supply. The installation must be preceded by a circuit-breaker with at least a 3 mm Electrical installation and service breaking gap.
NOTE! However, there is always 4 minutes between each step size (see the table under the heading “Output control immersion heater”). EVC 13 has an in- tegrated self-test program. This is activated by holding down the quick start button, and then pressing the restart button.
The electrical connection is made on the 1.96 1.47 relay card's (29) terminal block (14). 1.60 1.27 1.31 1.09 Max. permitted cable length: 1.08 0.94 Cu-cable Ø 0.6 mm 20 m 0.746 0.70 Cu-cable 1.0 mm 80 m 0.525 0,51 EVC 13...
When the system has stabilised (correct pressure in the boiler and all air removed) the heating controls can be set at the required value. See the section “Settings” - “Heating control system” and “Front panel. EVC 13...
Strömställarläge Position 0 Läge 0 Position 1 Läge 1 Position 2 Läge 2 Position n Läge R N L1 L2 L3 D A N NOTE! Terminal 26 is live even when the switch is in the 0 position. EVC 13...
Dimensions and setting-out coordinates Free space for air gap Fritt utrymme för luftspalt Floor Golv Skyddsklenspänning Protective low voltage Supply, electric boiler Matning, elpanna Tariff control, VVB Tariffstyrning, vvb * Free space for inspection and service. Measuring principle Compression ring Klämring EVC 13...
Fuse and tariff kits for the power supply of an external electrical hot water heater Components in the fuse and tariff kits are fitted in EVC 13 in the pre- pared places. Electrical connection is done according to the electrical circuit diagram below.
Fuse pressure 2.5 bar (0.25 MPa) Max thermostat setting 30 – 85 °C Expansion vessel volume 12 litres Part no. 089 300 Enclosed kits Outside sensor Current sensors 3 x Part no. 018 764 Part no. 018 569 EVC 13...
Page 28
Fax: 22 90 66 09 Jerikoveien 20 E-mail: info@nibe.se 1067 Oslo www.nibe-villavarme.no Tel: 085 662 84 90 NIBE-BIAWAR Sp. z o. o. Fax: 085 662 84 14 Aleja Jana Pawła II 57 E-mail: sekretariat@biawar.com.pl 15-703 BIAŁYSTOK www.biawar.com.pl Tel: +46 - (0)433 - 73 000...