Maximum altern-
NOTE!
ating current fuse
protection
National regulations, the grid operator's specifications or other factors may
require a residual current circuit breaker in the AC connection lead.
For this situation, a type B residual-current circuit breaker is generally adequate.
However, false alarms can be triggered for the type B residual current circuit breaker in
individual cases and depending on local conditions. For this reason, in accordance with
national legislation, Fronius recommends that a residual current protection device with a
tripping current of at least 1000mA suitable for frequency converters be used.
NOTE!
The inverter can be used with max. an automatic circuit breaker 355 A.
Inverter
Fronius Tauro 50-3
Fronius Tauro Eco 50-3
Fronius Tauro Eco 99-3
Fronius Tauro Eco 100-3
Changing the
The clamping area of the V-type terminal when delivered is 25 - 150 mm². A simple con-
clamping area for
version of the V-type terminal can change the clamping area to 185 - 300 mm².
V-type terminal
36
Phases
Nominal output
3
50 kVA
3
50 kVA
3
99 kVA
3
100 kVA
Max. fuse rating
3 x 355 A
3 x 355 A
3 x 355 A
3 x 355 A