Table 24 - Building Pressure Transducer Output; Table 25 - Ams Pressure Trans Duc Er Output; Table 26 - Discharge Pressure Transducer Output - York eco2 050 Installation Operation & Maintenance

Packaged rooftop air conditioning units
Hide thumbs Also See for eco2 050:
Table of Contents

Advertisement

TABLE 24 –BUILDING PRESSURE TRANS DUC ER
OUTPUT TABLE
BUILDING PRESSURE TRANSDUCER OUTPUT
DIFFERENTIAL INPUT
PRESSURE - IWG
-0.50
-0.40
-0.30
-0.20
-0.10
0.00
0.10
0.20
0.30
0.40
0.50
Air Measuring Station Pressure Transducer
The rooftop unit provides for a ventilation mode that
can use the optional Air Measuring Station. When us-
ing the optional Air Measuring Station, either one or
two identical pressure transducers are employed. When
using the Minimum AMS or the ¼ - ¾ AMS, two trans-
duc ers are used. Only one transducer is used with the
Full AMS. In any case, the locations of the transducers
are in the return air section mounted on a panel. Both
the pneumatic tubing and control wiring are factory
in stalled. The transducer range is 0 to .25 iwg with an
output range in volts DC as shown in Table 25.
TABLE 26 – DISCHARGE PRESSURE TRANSDUCER OUTPUT
INPUT PRESSURE - PSIG
0
20
40
60
80
100
120
140
160
180
200
220
240
YORK INTERNATIONAL
OUTPUT VOLTAGE
- VDC
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
DISCHARGE PRESSURE TRANSDUCER OUTPUT TABLE
OUTPUT VOLTAGE - VDC
1.00
1.16
1.32
1.48
1.64
1.80
1.96
2.12
2.28
2.44
2.60
2.76
2.92
TABLE 25 –AIR MEASURING STATION
PRESSURE TRANSDUCER OUTPUT
AMS PRESSURE TRANSDUCER OUTPUT TABLE
DIFFERENTIAL INPUT
PRESSURE - IWG
0.000
0.025
0.050
0.075
0.100
0.125
0.150
0.175
0.200
0.225
0.250
Discharge Pressure Transducer
The optional discharge pressure transducer is located
in common discharge line of the tandem compressors
for each refrigerant circuit. The purpose of this trans-
duc er is to sense and convert the discharge pressure
to a DC voltage. The DC voltage is then sent to the
unit controller where it can control head pressure (with
op tion al low ambient kit), provide compressor unload-
ing, and display discharge pressure on the OptiLogic
dis play panel. The transducer and wiring are factory
in stalled. Whenever an optional transducer package is
supplied, the transducer is wired to a factory supplied
INPUT PRESSURE - PSIG
260
280
300
320
340
360
380
400
420
440
460
480
500
FORM 100.50-NOM1 (604)
OUTPUT VOLTAGE
- VDC
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
4.00
4.50
5.00
TM
OUTPUT VOLTAGE - VDC
3.08
3.24
3.40
3.56
3.72
3.88
4.04
4.20
4.36
4.52
4.68
4.84
5.00