Troubleshooting Guidelines In Case Any Incoming - Siemens RAJA+ Installation, Maintenance & Troubleshooting Manual

Agriculture starters & controllers
Table of Contents

Advertisement

Installation, Maintenance & Troubleshooting guide | Version 02

2.6: Troubleshooting Guidelines in case any incoming

supply fault is present before switching ON the Starter
Table: 12 FASD starter operating sequence in fault condition
5A
5B
5C
3
LMR-A
Rocker
main
Mode
switch
supply
Manual
ON
ON
Auto
ON
ON
Bypass
ON
ON*
#: Phase loss
, Phase reversal
1
supply faults,only protection from load side faults. In this mode, amber LED will continously ON if incoming power supply is
healthy and will blink if the incoming power supply is unhealthy – Refer 2.8
Starter Fault conditon:
1) LMR-A: Manual mode
5A : Check the mode of LMR-A, if it is manual mode, please follow the below steps.
5B : Switches ON the 3-Phase incoming main supply.
5C : Switch ON the rocker switch
5D : Amber LED will start blinking
5E : Amber LED will blink for a duration of min.30sec.
5F : After the ON delay duration, amber LED remains blinking indicating that the 3phase incoming supply is unhealthy.
5G : - Check the rated operational voltage of the starter in incoming terminal block (TB1)between L1- L2 L2-L3, L1-L3
1
with suitable equipment e.g. multimeter.
- Check for the phase loss in any phase (L1,L2,L3) with suitable equipment e.g. multimeter.
5H: - After resuming incoming main supply to normal condition,
1
- Repeat the steps from 5A to 5E and then go to step no.5I
If fault still exists, then
5G : - Check the phase sequence of all the phases of incoming main supply.
2
- Identify the wrong sequence of phase connected in any of the incoming terminal.
5H: - Connect the phase sequence of all the phases correctly (R phase to L1 , Y phase to L2, B phase to L3) to the incoming main
2
supply terminals of Terminal block TB1.
- Repeat the steps from 5A to 5E and then go to step no.5I
If fault still exists, then
5G : - Check the rated operational voltage of the starter in incoming terminal block (TB1) between L1-L2, L2-L3, L1-L3 with
3
suitable equipment e.g. multimeter.
- Check whether the 3-phase voltage in the incoming terminals of terminal block TB1 is <minimum required voltage
(Refer table no.13).
5H : - Keep the 3-phase voltage to the incoming terminals of terminal block TB1 to a voltage between min.required voltage
3
& Max.voltage allowed (Refer table no.13).
- Repeat the steps from 5A to 5E and then go to step no.5I
5D
5E
Amber
On-
Amber
LED
Delay
Blink
(On-delay
0.5-5min
duration)
Blink
(On-delay
0.5-5min
duration)
Blink
(On-delay
0.5-5min
duration)
, Under voltage
, Over voltage
2
3
5F
5G
5H
Possible
Corrective
causes
LED
action
of fault
Blink
#
1)
Blink
#
2)
Blink
NA
NA
ON operation
, Phase unbalance
NA – Starter is unprotected from incoming power
4
5
5I
5J
5K
Amber
'ON' Push
Starter
LED
button
Operation
ON
ON
ON
ON
NA
ON
ON
ON
ON
5L
Green
LED
ON
ON
ON
20