Outputs - Kaba Access manager 92 32 Technical Manual

Table of Contents

Advertisement

Technical Manual
5.7.6

Outputs

5.7.6.1 OUT1 as potential-free switching contact
Kaba access manager 92 32
The access manager has 3 relay outputs OUT1 to OUT3.
Contact rating: 30 V AC/DC; 2 A max.
The outputs can be used for the activation of motor locks, door openers, turnstile
drives, technical alarm day/night, security alarm day/night etc.
The function of the individual outputs depends on the selected door template.
The wiring of the output OUT1 can be adjusted via jumper (1). The following variants
are possible as an alternative:
OUT1 is used as a potential-free contact
The internal 12 V DC power supply is switched to the output OUT1.
A power supply (max. 24 VAC) applied to the VREL terminal is switched to the
output OUT1
The external 24 V DC power supply (24 V EXT terminal) is switched to the output
OUT1.
The outputs OUT2 and OUT3 are designed permanently as potential-free relay out-
puts with one switching contact each.
1
Jumper for the wiring of output OUT1
2
Fuse F1 for protection of the power supply via OUT1
Fuse value: T2.5 A
The fuse is plugged in and can be replaced without problems.
The fuse F1 may only be replaced with fuses of the same type.
04045524 - 08/2016
Installation
35