5.3

Installation lines

5.3.1

Ethernet

5.3.2

Line to the door opener, the door opener key, and the door contacts

5.3.3

Coaxial cables to registration units

Kaba access manager 92 32
Network cable with RJ45 plug, line requirement: CAT.5 S-UTP 4 x 2 AWG 24 oder AWG
22 (according to EIA/TIA568) or higher quality.
Line requirements: Cable diameters from 0.5 mm to 0.8 mm.
Recommended cable: CAT.5 S-UTP 4 x 2 AWG 24 or AWG 22 (according to EIA/
TIA568) or higher.
Registration units are connected to the access manager via coaxial cables The coaxial
cable transfers the HF signals from the RFID antenna, keyboard data and trigger data
for the optical and acoustic signal generators.
Line requirements: Coaxial cable 50 ohms, type RG174/U.
Maximum cable length: 30 m
Recommended cable length: < 10 m