SIRAX BM1200 Архангельск (8182)63-90-72 Калининград (4012)72-03-81 Новосибирск (383)227-86-73 Сочи (862)225-72-31 Астана (7172)727-132 Калуга (4842)92-23-67 Омск (3812)21-46-40 Ставрополь (8652)20-65-13 Астрахань (8512)99-46-04 Кемерово (3842)65-04-62 Орел (4862)44-53-42 Сургут (3462)77-98-35 Барнаул (3852)73-04-60 Киров (8332)68-02-04 Оренбург (3532)37-68-04 Тверь (4822)63-31-35 Белгород (4722)40-23-64 Краснодар (861)203-40-90 Пенза (8412)22-31-16 Томск...
1. Introduction 1.1 Purpose of this document This document describes the universal measurement device SIRAX BM1200. It is intended to be used by: Installation personnel and commissioning engineers • Service and maintenance personnel • Planners • Scope This handbook is valid for all hardware versions of the BM1200. Some of the functions described in this doc-ument are available only, if the necessary optional components are included in the device.
3.1 Brief description The universal measuring device SIRAX BM1200 is suited for fi xed mounting and the measurement of Voltage, current, frequency, power, energy (active / reactive / apparent), power factor, phase angle, etc in low voltage switchgear. The units are designed for unbalanced load network forms of single-phase to 3-phase mains with 2-, 3- or 4-wire.
4. Mechanical mounting The SIRAX BM1200 is designed for panel mounting. Please ensure that the operating temperature limits are not exceeded when determining the place of mounting (place of measurement): –10 … +55° C 4.1 Panel cut out Dimensional drawing BM1200: See section 16 4.2 Mounting of the device...
Single wire: 1 x 0,5 … 4,0mm2 oder 2 x 0,5 … 2,5mm2 Multiwire with end splices: 1 x 0,5 … 4,0mm2 oder 2 x 0,5 … 2,5mm2 Tightening torque 0,5 … 0,6 Nm resp. 4,42 … 5,31 lbf in PM 1000266 000 01 Device handbook SIRAX BM1200 7/44...
7. Programming The following sections comprise step by step procedures for confi guring the SIRAX BM1200 according to in-dividual user requirements. To access the set-up screens press and hold ʺ UPʺ and ʺ DOWNʺ keys simultaneously for 5 seconds. This will take the User into the Password Protection Entry Stage (Section 7.1).
ʺPotential Transformer Primary Value Editʺ menu. (see section 7.2.1.2) Press the key ʺ Downʺ will return to the system type edit stage. Note: Default value is set to ʺ4ʺ i.e. 3P 4W PM 1000266 000 01 Device handbook SIRAX BM1200 13/44...
When the least signifi cant digit has been set, pressing the key ʺ This screen will only appear following an edit of the Current Transfor- UPʺ will advance to the ʺPotential Transformer secondary Value mer Primary Value. Confi rmationʺ stage. PM 1000266 000 01 Device handbook SIRAX BM1200 14/44...
UPʺ sets the displayed value and will advance scrolls the number back to 2. to Auto Scroll screen. (see section 7.2.1.7). NOTE: Default value is set to ‘8’ i.e. 8 min. PM 1000266 000 01 Device handbook SIRAX BM1200 15/44...
Wh, KWh rateʺ. and MWh. Pressing the key ʺ UPʺ accepts the present value and will advance to the ʺEnergy Rateʺ menu. (see section 7.2.1.12). PM 1000266 000 01 Device handbook SIRAX BM1200 16/44...
RS 485 port. Pressing the key ʺ UPʺ will select the value. Pressing the key ʺ UPʺ again will jump back to the Communication Parameter selection menu (see section 7.2.2). PM 1000266 000 01 Device handbook SIRAX BM1200 17/44...
If ʺ5ʺ or ʺ10ʺ option is selected, then it will advance to ʺUser Screen 1ʺ selection screen. NOTE: If User Screen feature is ON and System type is changed, then Active Energy screen (No. 8) is shown after exiting from setup. PM 1000266 000 01 Device handbook SIRAX BM1200 18/44...
This Screen Displays the total no. of times the Axillary Supply was Interrupted. Even if the Auxiliary supply is interrupted count will be maintained in internal memory. To reset No of Interruption manually see section Resetting Parameter 7.2.3. PM 1000266 000 01 Device handbook SIRAX BM1200 19/44...
Incorrect disposal can cause environ- mental risks. 14.5 Return All devices delivered to Camille Bauer Metrawatt AG shall be free of any hazardous contaminants (acids, lyes, solutions, etc.). Use original packaging or suitable transport packaging to return the device. Damage by returning Damages caused by improper returning, no warranties or guarantees can be given.
1A – 2mA (as per IEC 62053-21) 5A – 10mA Frequency: 50 Hz / 60 Hz Power factor: 0.5 Lag … 1 … 0.8 Lead Total Harmonic Distortion: 0 … 50% PM 1000266 000 01 Device handbook SIRAX BM1200 21/44...
Page 22
4 kV RMS 50 Hz for 1 minute between all electrical circuits High voltage test (Input vs Remaining circuit) 2 kV RMS 50 Hz for 1 minute between all electrical circuits PM 1000266 000 01 Device handbook SIRAX BM1200 22/44...
Page 23
Odd oder even, mit 1 Stop Bit, oder None mit 1 oder 2 Stop Bits Number of participants: < 32 Impulse Output Impulse constant: 110 V : 16000 impulse/kWh 230 V : 8000 impulse/kWh 415 V : 4000 impulse/kWh PM 1000266 000 01 Device handbook SIRAX BM1200 23/44...
Note : Number of registers = Number of parameters x 2 Each Query for reading the data must be restricted to 20 parameters or less. Exceeding the 20 parameter limit will cause a ModBus exception code to be returned. PM 1000266 000 01 Device handbook SIRAX BM1200 25/44...
Page 27
Vah / VAh Utility Overfl ow count • • • 30127 30131 30133 System Max Voltage • • • 30135 System Min Voltage • • • 30137 • • • 30141 System Max Currrent • • • PM 1000266 000 01 Device handbook SIRAX BM1200 27/44...
Page 28
Old Run Hour Utility • • • 30255 Old On Hour Utility • • • 30263 Old No. of Interruptions Utility • • • 30267 Relay Output 1 Status • • • PM 1000266 000 01 Device handbook SIRAX BM1200 28/44...
Page 29
For example, if user set update rate 15 min, then the values on these registers (marked with *) will get updated on every 15 min. 2. For model BM1200, energy is in terms of Import and Export. PM 1000266 000 01 Device handbook SIRAX BM1200 29/44...
Page 32
I2 THD (%) • • 44313 I3 THD (%) • • 44315 System Voltage THD (%) • • • 44317 System Current THD (%) • • • 44321 I Neutral • PM 1000266 000 01 Device handbook SIRAX BM1200 32/44...
Page 33
Old Reactive Energy Import / Utility 44925 Old Reactive Energy Export / GEN Overfl ow Count 44927 Old Reactive Energy Export / GEN 44929 Old Apparent Energy Utility Overfl ow Count 44931 Old Apparent Energy Utility PM 1000266 000 01 Device handbook SIRAX BM1200 33/44...
Number of register Hi: Most signifi cant 8 bits of Number of registers requested. Number of register Lo: Least signifi cant 8 bits of Number of registers requested. (Note: Two consecutive 16 bit register represent one parameter.) PM 1000266 000 01 Device handbook SIRAX BM1200 34/44...
Page 35
R/Wp 40113 User Screen 5 R/Wp 40115 User Screen 6 R/Wp 40117 User Screen 7 R/Wp 40119 User Screen 8 R/Wp 40121 User Screen 9 R/Wp 40123 User Screen 10 R/Wp PM 1000266 000 01 Device handbook SIRAX BM1200 35/44...
Page 36
fl oating point numbers are sent least signifi cant bytes fi rst. To set the mode, write the value ‘2141.0’ into this register-the instru-ment will detect the order used to send this value and set that order for all ModBus transaction involving fl oating point numbers. PM 1000266 000 01 Device handbook SIRAX BM1200 36/44...
Page 37
10 to TABLE 6 for screen numbers. Writing any other value will return an error. NOTE: Changing system type, PT/CT ratio, Energy Output, Energy Digit Reset Count will reset the energy. PM 1000266 000 01 Device handbook SIRAX BM1200 37/44...
Page 38
38400 NOTE: Codes not listed in the table above may give rise to unpredictable results including loss of communication. Exercise caution when attempt- ing to change mode via direct Modbus writes. PM 1000266 000 01 Device handbook SIRAX BM1200 38/44...
The actual address of the parameters (3X and 4X registers addresses) which are to be accessed via address 0x200 to 0x226 (or 0x1E00 to 0x1E26) are specifi ed in 4X Register 0x200 to 0x213. (see TABLE 11) PM 1000266 000 01 Device handbook SIRAX BM1200 39/44...
Power factor1,Wh import, Frequency send query with starting address 0x200 with number of register 8 or individually parameters can be accessed. For example, if current1 is to be accessed use starting address 0x212. (See section Reading Parameter data through User Assignable Registers). 17.5 Connection for RS485 Output RS 485 PM 1000266 000 01 Device handbook SIRAX BM1200 42/44...
Page 43
По вопросам продажи и поддержки обращайтесь: Архангельск (8182)63-90-72 Калининград (4012)72-03-81 Новосибирск (383)227-86-73 Сочи (862)225-72-31 Астана (7172)727-132 Калуга (4842)92-23-67 Омск (3812)21-46-40 Ставрополь (8652)20-65-13 Астрахань (8512)99-46-04 Кемерово (3842)65-04-62 Орел (4862)44-53-42 Сургут (3462)77-98-35 Барнаул (3852)73-04-60 Киров (8332)68-02-04 Оренбург (3532)37-68-04 Тверь (4822)63-31-35 Белгород (4722)40-23-64 Краснодар...