Kübler Sendix M3661 Manual

Kübler Sendix M3661 Manual

Analog (u/i), absolute multiturn encoder

Advertisement

Quick Links

Analog (U/I)
Manual
Absolute multiturn encoder
Sendix M3661 / M3681
Order code: 8.M36X1.XXXX.XX12
Sendix M3661R
Order code: 8.M3661R.XXXX.XX12
Sendix M5861
Order code: 8.M5861.XXXX.XX12

Advertisement

Table of Contents
loading

Summary of Contents for Kübler Sendix M3661

  • Page 1 Analog (U/I) Manual Absolute multiturn encoder Sendix M3661 / M3681 Order code: 8.M36X1.XXXX.XX12 Sendix M3661R Order code: 8.M3661R.XXXX.XX12 Sendix M5861 Order code: 8.M5861.XXXX.XX12...
  • Page 2 R60722.0002 - Index 3 Document no. Document name Manual - analog (U/I) Sendix M3661 / M3681, order code 8.M36X1.XXXX.XX12 Sendix M3661R, order code 8.M36X1R.XXXX.XX12 Sendix M5861, order code 8.M5861.XXXX.XX12 Language version English (ENG) - German is the original version...
  • Page 3: Table Of Contents

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 Table of contents 1. Technical details and encoder characteristics ............................4 1.1 Mechanical values ....................................4 1.2 Working temperature range ................................... 4 1.3 Supply voltage and current consumption ............................4 1.4 Load at the output / max.
  • Page 4: Technical Details And Encoder Characteristics

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 1. Technical details and encoder characteristics 1.1 Mechanical values Sendix M36x1 Shock resistance acc. to EN 60068-2-27 2500 m/s , 6 ms Vibration resistance acc. to EN 60068-2-6 300m/s , 10 …...
  • Page 5: Supported Standards And Functions

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 1.6 Supported standards and functions 8.M36X1.XX3X.3X12 / 8.M3661R.XX3X.3X12 / 8.M5861.XXXX.XX12: Output: 4 … 20mA Resolution: 12 bits Max. measuring range: 65536 revolutions Min. measuring range: 22.5° Zero point display: 0 … 1°...
  • Page 6: Electrical Installation

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 2. Electrical installation This chapter contains information about the electrical installation, commissioning of the absolute encoder M36X1 / M3661R / M5861 analog. 2.1 Electrical installation Switch off the plant! Make sure that the whole plant remains switched off during the whole electrical installation.
  • Page 7: Function And Status Led

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 3. Function and status LED The device is equipped with a two-color (green / red) LED displaying status and errors. 3.1 LED combinations during operation Display Meaning Error cause Addition •...
  • Page 8: Led Combinations For Scaling

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 3.2 LED combinations for scaling Display Meaning Error cause Addition • Green LED flashes 1x Activation of scaling input 1 detected and confirmed. • Green LED flashes 3x Activation of scaling input 2 detected.
  • Page 9: Scaling Function (Optional)

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 4.1 Scaling function (optional) The encoder is factory-set to a measuring range of 16 revolutions over which the corresponding output signal is scaled linearily. Two scaling inputs (set 1, set 2 - see chapter Terminal assignment) allow the user to define himself a desired measuring range.
  • Page 10: Reference Point Display

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 4.2 Reference point display With the factory-set „default“ scaling, the LED displays the reference point of 0..1°. The reference point display is no longer available if another measuring range is scaled using the scaling inputs.
  • Page 11: Limit Switch Function (Optional)

    Manual - analog (U/I) Sendix M3661 / M3681 Sendix M3661R Sendix M5861 4.5 Limit switch function (optional) With the limit switch function, the output signal does not remain at the last final value, but it makes a defined jump. This signal jump can be used by a control as a limit switch.
  • Page 12 www.kuebler.com Kübler Group Fritz Kübler GmbH Schubertstrasse 47 D-78054 Villingen-Schwenningen Germany Phone: +49 7720 3903-0 Fax: +49 7720 21564 info@kuebler.com www.kuebler.com...

This manual is also suitable for:

Sendix m3681Sendix m3661rSendix m5861