Remote Module LED Status Indicators

Symphony ® II System does not communicate or manage
appliances/loads when utility power is present.
NOTICE When looking at LED's, make sure you look straight on
and not at an angle.
Low Voltage (Single and Dual) Models
A
B
C
A - Low Voltage Control Wiring Terminal Contacts
B - Priority Selector
C - Power/Line Connection
D - Neutral Connection
E - Transparent plastic cover
F - Ground connection (optional)
G - Status LED
H - Plastic Barrier
H
G
F
D
E
Status LED (G) is used to indicate communication status.
Utility power present:
• Normal State
-
Orange LED - No communication and appliances/loads
cannot be managed by Symphony ® II System
• Problem State (see Troubleshooting)
-
No LED - No power to low voltage control board; verify
correct wiring
-
Green LED - Broken LED; replace low voltage module
-
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires
Generator power present:
• Normal State
-
Green LED - Signal communication detected and
appliances/loads can be managed after 5 minute delay
• Problem State (see Troubleshooting)
-
No LED - No power to low voltage control board; verify
correct wiring
-
Orange LED - Signal communication not detected; verify
correct wiring
-
Red LED - Fault in system; verify current transformer
connections, verify terminations on orange and yellow
communication wires
19