Safety Component Types; Safety Block Diagrams - ABB ACS880-07CLC User Manual

Emergency stop, stop category 0 (option +q951) for acs880-07clc drives
Hide thumbs Also See for ACS880-07CLC:
Table of Contents

Advertisement

36 Technical data
Drive type
Contact-
or
AF16 -
ACS880-07CLC
AF30
with option
6)
charging
+F272
contactor
1) Contactors installed by the user will have an effect on the safety data.
2) PFH values according to EN ISO 13849.
3) In low demand mode, DC of electromechanical devices is considered as 0%, and therefore no overall DC value is claimed
in low demand mode.
4) See also the Recommendation of Use CNB/M/11.050 published by the European coordination of Notified Bodies for lower
T
requirement.
1
5) T
= 20 a stands for high demand use. T
1
6) With internal charging circuit and charging contactor.
Note: If T
> 1 a is needed in low demand mode of operation, SIL 1 / PL c levels shall be
1
used and PFD calculated separately.

Safety component types

Safety component types as defined in IEC 61508-2:
• emergency stop button: type A
• safety relay(s): type A
• charging contactor: type A

Safety block diagrams

The components that are included in the safety data calculations are shown in the safety
block diagram(s). The components not included in the delivery are not included in the safety
data calculations.
1
1
Emergency stop button
2
Emergency stop safety relay
3
Safety relay
4
Charging contactor (option +F272)
5
Main contactor/breaker (user-defined)
2)
SIL /
PL
PFH
1)
SIL-
[1/h]
CL
2
d
5.02E-7
= 1 a is used with low demand mode of operation.
1
2
3)
PFD
SC
Cat.
DC
avg
[%]
5.9E-4
≥90
3
2
3
4
4) 5)
HFT
CCF
Mis-
T
1
sion
[a]
time
[a]
0
65
20
20 / 1
3AXD10000097591 K