Validation Test Reports; Start-Up And Validation Test - ABB ACS880-07CLC User Manual

Emergency stop, stop category 0 (option +q951) for acs880-07clc drives
Hide thumbs Also See for ACS880-07CLC:
Table of Contents

Advertisement

26 Start-up and validation test

• you must document all validation tests
• you must sign and store the validation test report for further reference.

Validation test reports

You must store the signed validation test reports in the logbook of the machine. The report
must include, as required by the referred standards:
• a description of the safety application (including a figure)
• a description and revisions of safety components that are used in the safety application
• a list of all safety functions that are used in the safety application
• a list of all safety-related parameters and their values
• documentation of start-up activities, references to failure reports and resolution of failures
• the test results for each safety function, checksums, date of the tests, and confirmation
by the test personnel.
You must store any new validation test reports done due to changes or maintenance in the
logbook of the machine.
Start-up and validation test
You must use the Drive composer PC tool or a control panel to do the start-up and validation
test.
Action
WARNING!
Obey the safety instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
Initial status
Make sure that the drive is ready for use, that is, you have done the tasks of the drive start-up procedure.
See the hardware manual.
Make sure that the STO function is configured and validated. See the hardware manual.
Checks and settings with no voltage connected
Stop the drive and do the steps in section
work.
If you have done any connections for the emergency stop circuit on site (such as wiring of additional
emergency stop buttons, connection of shipping splits of large drives, etc.), check the connections
against the applicable circuit diagrams.
Inverter units with parallel R8i inverter modules:
Make sure that the XSTO.OUT output on the inverter control unit [A41] is chained to the STO inputs of
all inverter modules.
Make sure that the hardware settings of the safety function are set as defined in this manual.
Settings with voltage connected
Close the cabinet doors and power up the drive. See the hardware manual.
Make sure that the parameter settings related to the safety functions are correct. See chapter
settings.
Electrical safety precautions (page 9)
before you start the
Parameter