Section 4
Configuring bay protection using HMI500
IEC18000650 V1 EN-US
Figure 13:
General purpose
The General Purpose tab provides facility for defining up to 20 user signals. To this end, select
a signal number with the left mouse button. A text field appears in which the user can write a
signal name (see
conventions (see
signals of BP in REB500 Technical manual - Bay protection functions provides a list of all
signals available for general purpose inputs.
Example:
Signal name under the BP function
Ext Blk Dist
20
Configuring binary inputs (Default → Output from SP function)
Location of input signals from SP function within the BP function diagram see
Figure
1, Label number 15.
Figure
14). The signal name entered must conform to REB500 signal
REB500 Technical manual - Bay protection functions ). Section Binary input
© 2019 - 2020 Hitachi Power Grids. All rights reserved
Designation of binary input signals to be entered
under General Purpose
111205_DIST Ext. Block Dist.
1MRK 505 403-UEN Rev. C
17000030-IEC18000650-1-en.vsdx
Bay protection functions REB500
Application manual