1MRK 505 403-UEN Rev. C
Table 7:
Menu item
Copy
Delete
Properties
Status indicator
On the left of each instance number and function symbol there is a status indicator which
signals the validity of the parameters entered.
17000024-IEC18000644-1-en.vsdx
IEC18000644 V1 EN-US
Figure 7:
Green indicates that the configuration is correct and valid while red indicates that the setting
procedure has not been completed. This generally means in the case of a single-phase function
that an analogue channel has not yet been assigned to it.
The Bay protection dialog box cannot be closed by clicking OK until all the status indicators
are green.
Statistical evaluation
Double-clicking with the right mouse button with the cursor in the dialog box below the area
of the tabs opens a window with statistics and status information on the bay protection
functions.
Bay protection functions REB500
Application manual
Content menu dialog boxes
Description
Creates a copy of the protection function according to the following
rules:
A copy cannot be in the same parameter set as the original.
The input signals of a copy are the same as those of the original
and cannot be changed.
Only defined parameters of a copy can be configured. All other
parameters are taken from the original.
The instance of the specific protection function is deleted together with
all the settings that the user has made up to that point.
If the function being deleted has connections to other protection
functions, an error message appears instructing you to first delete the
connections.
Thus an instance can only be deleted after all its interconnections have
been deleted.
This opens a dialog with all the function's settings. Double-clicking on
the function's symbol opens the same dialog box.
Status indication of BP function