REPLACING FURNACE THAT WAS PART OF A
COMMON VENT SYSTEM
CHIMNEY
OR GAS
VENT
(Check sizing
for water
heater only)
FURNACE
(Replaced)
If replacing a furnace which was
commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the single water heater or other appliance. The vent
should be checked for proper draw with the remaining
appliance.
Figure 22
Exhaust Piping (Figure 25 and Figure 26)
Route piping to outside of structure. Continue with instal-
lation following instructions given in piping termination
section.
CAUTION
Do not discharge exhaust into an existing stack or
stack that also serves another gas appliance. If vertical
discharge through an existing unused stack is required,
insert PVC pipe inside the stack until the end is even
with the top or outlet end of the metal stack.
CAUTION
The exhaust vent pipe operates under positive pressure
and must be completely sealed to prevent leakage of
combustion products into the living space.
Vent Piping Guidelines
NOTE -
WATER
HEATER
OPENINGS
(To Adjacent
Room)
-
-
-
-
Page 17
The EL196UHE can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE - In Non-Direct Vent installations, combustion air
TABLE 4, TABLE 5 and TABLE 6. Count all elbows inside
and outside the home.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination
it exits the termination. Refer to TABLE 8.
In some applications which permit the use of several dif-
used. Contact Lennox' Application Department for assis-
NOTE -
Horizontal Installation Offset Requirements
Exhaust Pipe
Horizontal
Gas Furnace
12" ma x
of straight pip e
NOTE -
ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm)
of horizontal run is mandatory for drainage.
NOTE - Exhaust pipe MUST be glued to furnace exhaust fittings.
NOTE - Exhaust piping should be checked carefully to make
sure there are no sags or low spots.
Figure 23
TABLE 4
MINIMUM VENT PIPE LENGTHS
EL196UHE Model
030, 045, -070, -090, 110
*Any approved termination may be added to the minimum
length listed. Two 45 degree elbows are the equivalent to one
90 degree elbow.
12" Min .
MIN. VENT LENGTH*
15 ft. or 5 ft. plus 2 elbows
or 10 ft. plus 1 elbow
-
-
-