Lennox ELITE Series Installation Instructions Manual

Lennox ELITE Series Installation Instructions Manual

Upflow / horizontal air discharge

Advertisement

© 2020 Lennox Industries Inc.
Dallas, Texas USA
Contents
Unit Dimensions - inches (mm) ......................................2
EL296UHE Gas Furnace ................................................3
Shipping and Packing List ..............................................3
Safety .............................................................................3
General ...........................................................................5
Combustion, Dilution, Ventilation Air...............................5
Setting Equipment ..........................................................8
Filters ............................................................................12
Duct System .................................................................12
Pipe Fittings Specifications...........................................12
Joint Cementing Procedure ..........................................13
Venting Practices ..........................................................14
C C C C
I I I I
HI
HI
INSTALLATION
INSTRUCTIONS
EL296UHE
ELITE
SERIES GAS FURNACE
®
UPFLOW / HORIZONTAL AIR DISCHARGE
507280-05
08/2020
Supersedes 06/2020
THIS MANUAL MUST BE LEFT WITH THE
HOMEOWNER FOR FUTURE REFERENCE
This is a safety alert symbol and should never be
ignored. When you see this symbol on labels or in man-
uals, be alert to the potential for personal injury or death.
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, personal
injury or loss of life. Installation and service must be
performed by a licensed professional HVAC installer (or
equivalent), service agency or the gas supplier.
As with any mechanical equipment, contact with sharp
sheet metal edges can result in personal injury. Take
care while handling this equipment and wear gloves and
protective clothing.
Gas Piping ....................................................................35
Electrical .......................................................................37
Integrated Control .........................................................40
Unit Start-Up .................................................................46
Gas Pressure Measurement.........................................47
Proper Combustion.......................................................48
High Altitude .................................................................48
Other Unit Adjustments.................................................49
Sequence of Operation.................................................50
Service..........................................................................51
Repair Parts List ...........................................................52
Start-Up and Perormance Checklist .............................55
Blower Data ..................................................................57
Page 1
WARNING
CAUTION

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ELITE Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Lennox ELITE Series

  • Page 1: Table Of Contents

    INSTALLATION INSTRUCTIONS EL296UHE © 2020 Lennox Industries Inc. Dallas, Texas USA ELITE SERIES GAS FURNACE ® UPFLOW / HORIZONTAL AIR DISCHARGE 507280-05 08/2020 Supersedes 06/2020 THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE This is a safety alert symbol and should never be ignored.
  • Page 2: Unit Dimensions - Inches (Mm)

    EL296UHE Unit Dimensions - inches (mm) NOTE - 60C and 60D size units that require air volumes over 1800 cfm must have one of the following: 1. Single side return air and Optional Return Air Base with transition that must accommodate required 20 x 25 x 1 inch (508 x 635 x 25 mm) air filter to EXHAUST AIR 3-1/4...
  • Page 3: El296Uhe Gas Furnace

    EL296UHE Gas Furnace Shipping and Packing List The EL296UHE Category IV gas furnace is shipped ready Package 1 of 1 contains for installation in the upflow or horizontal position. The fur- nace is shipped with the bottom panel in place. The bot- 1 - Assembled EL296UHE unit tom panel must be removed if the unit is to be installed 1 - Bag assembly containing the following:...
  • Page 4: Use Of Furnace As A Construction Heaterl

    In Canada, installation must conform with current National Heating Unit Installed Parallell to Air Handler Unit Standard of Canada CSA-B149 Natural Gas and Propane Dampers Installation Codes, local plumbing or waste water codes (open during heating operation only) and other applicable local codes. Gas Unit In order to ensure proper unit operation in non-direct vent applications, combustion and ventilation air supply must...
  • Page 5: General

    FAILURE TO FOLLOW THE ABOVE INSTALLATION IN- STRUCTIONS VOIDS THE MANUFACTURER’S EQUIP- Permanent wave solutions MENT LIMITED WARRANTY. LENNOX DISCLAIMS Chlorinated waxes and cleaners ALL LIABILITY IN CONNECTION WITH INSTALLER’S Chlorine base swimming pool chemicals FAILURE TO FOLLOW THE ABOVE INSTALLATION IN- Water softening chemicals STRUCTIONS.
  • Page 6 A portion of this information has been reprinted with per- When the furnace is installed so that supply ducts carry mission from the National Fuel Gas Code (ANSIZ223.1/ air circulated by the furnace to areas outside the space NFPA 54). This reprinted material is not the complete and containing the furnace, the return air must be handled by official position of the ANSI on the referenced subject, ducts which are sealed to the furnace casing and which...
  • Page 7 Air from Outside EQUIPMENT IN CONFINED SPACE (Inlet Air from Ventilated Crawlspace and Outlet Air to Outside) If air from outside is brought in for combustion and ventila- tion, the confined space shall be provided with two perma- nen openings. One opening shall be within 12” (305mm) Roof Terminated of the top of the enclosure and one within 12”...
  • Page 8: Setting Equipment

    Installation - Setting Equipment EQUIPMENT IN CONFINED SPACE - ALL AIR FROM OUTSIDE WARNING ROOF TERMINATED EXHAUST PIPE Do not connect the return air duct to the back of the furnace. Doing so will adversely affect the operation of the safety control devices, which could result in personal OUTLET AIR injury or death.
  • Page 9 Return Air Guidelines WARNING Return air can be brought in through the bottom or either Improper installation of the furnace can result in side of the furnace installed in an upflow application. If the personal injury or death. Combustion and flue products furnace is installed on a platform with bottom return, make must never be allowed to enter the return air system an airtight seal between the bottom of the furnace and the...
  • Page 10 Optional Return Air Base CONDENSATE (Upflow Applications Only) TRAP FURNACE FRONT 23 (584) 3−1/4 IF BASE Overall (83) IS USED (Maximum) Minimum WITHOUT 11 (279) IAQ CABINET, Maximum 22−7/16 INDOOR AIR A SINGLE Unit side return air 14 (356) (570) QUALITY RETURN AIR Opening...
  • Page 11 FIGURE 18, or install the furnace installation according to instructions. on a platform, as shown in FIGURE 19. A horizontal sus- pension kit (51W10) may be ordered from Lennox or use *GAS CONNECTION INTAKE PIPE equivalent.
  • Page 12: Filters

    NOTE - Return air must not be drawn from a room specifications provided by the filter manufacturer against where this furnace, or any other gas-fueled appliance the data given in the appropriate Lennox Product (i.e., water heater), or carbon monoxide-producing de- Specifications bulletin. Additional information is provided vice (i.e., wood fireplace) is installed.
  • Page 13: Joint Cementing Procedure

    CAUTION Pipe & Fittings Specifications All pipe, fittings, primer and solvent cement must conform Solvent cements for plastic pipe are flammable liquids with American National Standard Institute and the Ameri- and should be kept away from all sources of ignition. can Society for Testing and Materials (ANSI/ASTM) stan- Do not use excessive amounts of solvent cement when dards.
  • Page 14: Venting Practices

    NOTE - Time is critical at this stage. Do not allow 2 - When furnace is installed in a residence where unit is shut down for an extended period of time, such primer to dry before applying cement. as a vacation home, make provisions for draining 6 - Promptly apply solvent cement to end of pipe and condensate collection trap and lines.
  • Page 15 7 - If a venting problem is found during any of the Vent Piping Guidelines preceding tests, the common venting system must NOTE - Lennox has approved the use of DuraVent® and be modified to correct the problem. Centrotherm manufactured vent pipe and terminations Resize the common venting system to the minimum as an option to PVC.
  • Page 16 *Any approved termination may be added to the minimum length list- ed. Two 45 degree elbows are equivalent to one 90 degree elbow. NOTE - Lennox offers a glueless vent adapter kit 17H92 as an option for exhaust exiting at the furnace top cap...
  • Page 17 TABLE 4 OUTDOOR TERMINATION USAGE* STANDARD CONCENTRIC Wall Kit 1-1.2 inch 2 inch 3 inch Flush Mount Vent Pipe 2 inch 3 inch Input Size Field 71M80 (US) 69M29 (US) 60L46 (US) Dia. in. 51W11 (US) Fabricated 44W92 44W92 44W93 22G44 (US) 44J40 (US) 51W12...
  • Page 18 TABLE 5 Maximum Allowable Intake or Exhaust Vent Length in Feet NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size Standard Termination at Elevation 0 - 4500 ft Number 2”...
  • Page 19 TABLE 5 Continued Maximum Allowable Intake or Exhaust Vent Length in Feet NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size. Concentric Termination at Elevation 0 - 4500 ft Number 2”...
  • Page 20 TABLE 6 Maximum Allowable Exhaust Vent Lengths With Furnace Installed in a Closet or Basement Using Ventilated Attic or Crawl Space For Intake Air in Feet NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and Exhaust must be same pipe size.
  • Page 21 TYPICAL EXHAUST AND INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR NON-DIRECT VENT APPLICATIONS EXHAUST INTAKE EXHAUST INTAKE 2” 2” 2” 2” 3” 3” TRANSITION TRANSITION 2” 2” *2” *2” DO NOT transition from smaller to larger pipe in horizontal runs of exhaust pipe.
  • Page 22 Intake Piping TYPICAL AIR INTAKE PIPE CONNECTIONS HORIZONTAL NON−DIRECT VENT APPLICATIONS The EL296UHE furnace may be installed in either direct (Horizontal Right−Hand Air Discharge Application Shown) vent or non-direct vent applications. In non-direct vent ap- plications, when intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines listed in Combustion, Dilution and Ventilation Air section must be followed.
  • Page 23 General Guidelines for Vent Terminations CAUTION In Non-Direct Vent applications, combustion air is taken If this unit is being installed in an application with from indoors or ventilated attic or crawlspace and the flue combustion air coming in from a space serviced by an gases are discharged to the outdoors.
  • Page 24 TABLE 7 Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For Winter Design Temperatures Two - Stage High Efficiency Furnace Winter Design Unit Input Size Vent Pipe Temperatures1 °F Diameter (°C) 32 to 21 2 in (0 to -6) 2-1/2 in 3 in...
  • Page 25 ‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible. FIGURE 32...
  • Page 26 ‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor. Lennox recommends avoiding this location if possible. FIGURE 33 Page 26...
  • Page 27 Details of Intake and Exhaust Piping Terminations for TABLE 8 Direct Vent Installations EXHAUST PIPE TERMINATION SIZE REDUCTION NOTE - In Direct Vent installations, combustion air is taken EL296UHV MODEL Termination Pipe Size from outdoors and flue gases are discharged to outdoors. *045 and 070 1-1/2”...
  • Page 28 7 - If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, piping must be supported. At least FIELD-PROVIDED Accelerator not required REDUCER MAY BE one bracket must be used within 6” from the top of for 3”...
  • Page 29 FIELD FABRICATED WALL TERMINATION NOTE − FIELD−PROVIDED REDUCER MAY BE 2” (51mm) 3” (76mm) REQUIRED TO ADAPT LARGER VENT PIPE SIZE Vent Pipe Vent Pipe TO TERMINATION A− Minimum clearance above grade or average 12” (305 mm) 12” (305 mm) snow accumulation B−...
  • Page 30 Crawl Space and Extended Horizontal Venting inside trated. In any exterior portion of chimney, the exhaust vent must be insulated. Lennox provides kit 51W18 (USA) and kit 15Z70 (Cana- FIGURE 45 da) to install 2” or 3” PVC exhaust piping through the floor Condensate Piping joists and into the the crawl space.
  • Page 31 Heating cable kit is coil can drain together. See FIGURE 49, FIGURE available from Lennox in various lengths; 6 ft. (1.8m) - 52( upflow furnace) and FIGURE 53. kit no. 26K68 and 24 ft. (7.3m) - kit no. 26K69.
  • Page 32 CONDENSATE TRAP LOCATIONS Furnace With Evaporator Coil Using A Separate Drain (Unit shown in upflow position with remote trap) FieldProvidedVent Evaporator drain Min. 1” Above Condensate line required Drain Connection (Trap at coil is optional) 1” Min. 2” Max. Field Provided Vent (1”...
  • Page 33 Furnace with Evaporator Coil Using a Separate Drain (Unit shown in horizontal left-hand discharge position) Field Provided Vent Evaporator (4” min. to 5” max. above Coil condensate connection) 4”min 5”max 5’ max. PVC Pipe Only Condensate Drain Connection (Trap at coil is optional) Drain Pan Piping from furnace and evaporator coil must slope down a minimum 1/4”...
  • Page 34 TRAP / DRAIN ASSEMBLY USING 1/2” PVC OR 3/4” PVC Optional Condensate Drain Connection Adapter 3/4 inch slip X 3/4 inch mpt (not furnished) 90° Street Elbow 3/4 inch PVC (not furnished) Adapter 3/4 inch slip X 3/4 inch mpt (not furnished) Condensate Drain Connection In Unit 1 (25 mm) Min.
  • Page 35: Gas Piping

    IMPORTANT Gas Piping Gas supply piping should not allow more than 0.5”W.C. Compounds used on threaded joints of gas piping must drop in pressure between gas meter and unit. Supply gas be resistant to the actions of liquified petroleum gases. pipe must not be smaller than unit gas connection.
  • Page 36 Upflow Application Upflow Application Left Side Piping Right Side Piping (Standard) (Alternate) 1/2” NPT 1/2” NPT MANUAL MAIN SHUT-OFF VALVE MANUAL MAIN SHUT-OFF VALVE GROUND GROUND JOINT JOINT UNION UNION DRIP LEG FIELD PROVIDED AND INSTALLED DRIP LEG NOTE - BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET FIGURE 56 Horizontal Applications Possible Gas Piping Configurations...
  • Page 37: Electrical

    TABLE 9 Gas Pipe Capacity - ft3/hr (m3/hr) Nominal Internal Length of Pipe - feet (m) Iron Pipe Diameter Size Inches inches (3.048) (6.096) (9,144) (12,192) (15.240) (18.288) (21.336) (24.384) (27.432) (30,480) (mm) (mm) .622 (12.7) (17.799) (4.87) (3.34) (2.69) (2.29) (2.03) (1.84)
  • Page 38 Electrically ground the unit according to local codes or, • The furnace requires 120 volts + 10% (Range: 108 in the absence of local codes, according to the current volts to 132 volts). National Electric Code (ANSI/NFPA No. 70) for the USA •...
  • Page 39 FIGURE 59 Page 39...
  • Page 40: Integrated Control

    Integrated Control 24VAC Indoor Blower Terminals Ignitor and Combustion Air Inducer Neutrals Flame Sense S4 DIP Switches Diagnostic Push Button On Board Links 3/16” QUICK CONNECT TERMINALS THERMOSTAT CONNECTIONS (TB1) DS = DEHUMIDIFICATION SIGNAL FLAME SENSE SIGNAL W2 = HEAT DEMAND FROM 2ND STAGE T/STAT HI Cool 24VAC W1 = HEAT DEMAND FROM 1ST STAGE T/STAT HI HEAT 24VAC...
  • Page 41 The unit is shipped from the factory with a blower-off delay Integrated Control DIP Switch Settings of 90 seconds. The blower off delay affects comfort and EL296UHE units are equipped with a two-stage integrat- is adjustable to satisfy individual applications. Adjust the ed control.
  • Page 42 TABLE 13 EL296 Field Wiring Applications With Conventional Thermostat DIP Switch Settings and On-Board Links DIP Switch 1 On Board Links Must Be Cut To Select Thermostat Thermostat Wiring Connections System Options Heating Stages 1 Heat / 1 Cool FURNACE OUTDOOR T'STAT TERM.
  • Page 43 TABLE 13 EL296 Field Wiring Applications With Conventional Thermostat (Continued) DIP Switch Settings and On-Board Links DIP Switch 1 On Board Links Must Be Cut To Select Thermostat Thermostat Wiring Connections System Options Heating Stages 2 Heat / 2 Cool FURNACE OUTDOOR T'STAT...
  • Page 44 TABLE 13 EL296 Field Wiring Applications With Conventional Thermostat (Continued) DIP Switch Settings and On-Board Links DIP Switch 1 Wiring Connections Thermostat On Board Links Must Be Cut To Select Thermostat Heating System Options Stages FURNACE HEAT PUMP Dual Fuel T'STAT TERM.
  • Page 45 TABLE 13 EL296 Field Wiring Applications With Conventional Thermostat (Continued) DIP Switch Settings and On-Board Links DIP Switch 1 Wiring Connections Thermostat On Board Links Must Be Cut To Select Thermostat Heating System Options Stages FURNACE HEAT PUMP Dual Fuel T'STAT TERM.
  • Page 46: Unit Start-Up

    6 - Adjust the thermostat to deactivate the heating Unit Start-Up demand and wait for the combustion air inducer to FOR YOUR SAFETY READ BEFORE OPERATING stop. At this point, the trap should be primed with sufficient water to ensure proper condensate drain WARNING operation.
  • Page 47: Gas Pressure Measurement

    1 - When thermostat calls for heat, combustion air NOTE - Pressure test adapter kit (10L34) is available from inducer starts. Lennox to facilitate manifold pressure measurement. 2 - Combustion air pressure switch proves blower A manifold pressure post located on the gas valve pro- operation.
  • Page 48: Proper Combustion

    Proper Combustion High Altitude Information Furnace should operate minimum 15 minutes with correct NOTE - In Canada, certification for installations at eleva- manifold pressure and gas flow rate before checking com- tions over 4500 feet (1372 m) is the jurisdiction of local bustion.
  • Page 49: Other Unit Adjustments

    6 - Follow the lighting instruction to place the appliance Testing for Proper Venting and Sufficient Combus- being inspected into operation. Adjust thermostat so tion Air for Non-Direct Vent Applications appliance will operate continuously. WARNING 7 - Use the flame of match or candle to test for spillage of flue gases at the draft hood relief opening after 5 minutes of main burner operation.
  • Page 50: Sequence Of Operation

    7 - When the demand for high fire (second stage) heat Heating Sequence of Operation is satisfied, the combustion air inducer is switched to Electronic Ignition the low-fire heating speed and the high-fire (second stage) gas valve is de-energized. The low-fire (first The two-stage, variable speed integrated control used stage) gas valve continues operation.
  • Page 51: Service

    At the beginning of each heating season, and to comply and operation. Consult Service Literature for proper with the Lennox Limited Warranty, your system should be combustion values. checked as follows: 14- Verify operation of CO detectors and replace 1 - Check wiring for loose connections, voltage at batteries as required.
  • Page 52: Repair Parts List

    3 - Clock gas meter to ensure that the unit is operating at Repair Parts List the specified firing rate for each stage of operation. The following repair parts are available through Lennox Check the supply pressure and the manifold pressure dealers. When ordering parts, include the complete fur- on both low fire and high fire.
  • Page 53 Requirements for Commonwealth of Massachusetts Modifications to NFPA-54, Chapter 10 4 - INSPECTION. The state or local gas inspector of the side wall, horizontally vented, gas-fueled equipment Revise NFPA-54 section 10.8.3 to add the following shall not approve the installation unless, upon requirements: inspection, the inspector observes carbon monoxide For all side wall, horizontally vented, gas-fueled equip-...
  • Page 54 ADDENDUM FOR ALL PROVINCES OF CANADA See below for venting in all provinces of Canada. Lennox approves the following termination for use in all provinces of Canada. 12” 2” (51MM) 3” (76MM) Vent Pipe Vent Pipe A − Clearance above grade or 12”...
  • Page 55: Start-Up And Perormance Checklist

    Start-Up & Performance Check List UNIT SET UP (typical) Furnace: Model Number_______________ Serial Number_________________ SUPPLY Line Voltage GAS SUPPLY LP Propane Gas Natural Gas Piping Connections Tight Leak Tested Flter Supply Line Pressure “W.C.________ RETURN AIR Gas Supply Pressure DUCT SYSTEM SUPPLY AIR DUCT Sealed INTAKE / EXHAUST PIPE...
  • Page 56 UNIT OPERATION HEATING MODE COOLING MODE GAS MANIFOLD PRESSURE “W.C._____ INDOOR BLOWER AMPS______ COMBUSTION SAMPLE CO CO PPM_______ TEMPERATURE DROP ______ Return Duct Temperature _________ INDOOR BLOWER AMPS______ Supply Duct Temperature _______ Temperature Drop = _________ TEMPERATURE RISE TOTAL EXTERNAL STATIC (dry coil) Supply Duct Temperature ________ Supply External Static _______ Return Duct Temperature...
  • Page 57: Blower Data

    Blower Data EL296UH045XE36B PERFORMANCE (Less Filter) Air Volume / Watts at Various Blower Speeds External Static High Medium-High Medium Medium-Low Pressure (Black) (Brown) (Blue) (Yellow) (Red) in. w.g. Watts Watts Watts Watts Watts 0.00 1345 1255 1150 0.10 1305 1225 1105 0.20 1290...
  • Page 58 Blower Data EL296UH110XE60C PERFORMANCE (Less Filter) Air Volume / Watts at Different Blower Speeds Single Side Return Air − Air volumes in bold require Bottom Return Air, Side Return Air with Return Air from Both Optional Return Air Base and field fabricated transition to External Sides or Return Air from Bottom and One Side.
  • Page 59 TABLE 18 Allowable Heating Speeds EL296UH Low Fire Heating Speeds High Fire Heating Speeds Model Yellow Blue Brown Black Yellow Blue Brown Black Number 045XE36B Allowed Factory 070XE36B Allowed Setting Allowed 090XE48C Allowed Allowed Allowed Allowed Allowed Allowed Allowed 110XE60C Factory Allowed Setting...