Testing The Combustion Parameters - Wolf CGS-2-14/120L Installation Instructions Manual

Hide thumbs Also See for CGS-2-14/120L:
Table of Contents

Advertisement

The condensing boiler is equipped with electronic combustion control which ensures optimum combustion quality. For a detailed
description of combustion control, see chapter "Combustion air control".
During commissioning and maintenance, only a check of the CO, CO
the boiler closed.
A flue gas test by a contractor is necessary after every modification of the GBC-e PCB, mixing device, burner or gas
Please
valve.
note
Note:
The combustion control carries out an automatic
calibration after every boiler start. This can lead
to briefly increased CO emissions. Therefore, test
the emissions no sooner than 60 seconds after
the burner has started.
Testing the intake air
1. Remove screw A from the left hand test port.
2. Open the gas ball valve.
3. Insert the test probe.
4. Switch ON the condensing boiler and select Emissions
test via the function keys.
5. Check the temperature and CO
6. In the case of a concentric balanced flue, the flue is not
gas-tight if the CO
content is > 0.3 %. The leak must be
2
rectified.
7. After the test has been completed, switch the appliance
off, remove the test probe and close the test port. Ensure
the screws are tightly secured.
Testing the flue gas parameters while the appli-
ance is closed
When the test port is open, flue gas can escape
Please
into the installation room. There is a risk of as-
note
phyxiation.
1. Remove screw B from the right hand test port.
2. Open the gas ball valve.
3. Insert the test probe.
4. Switch ON the condensing boiler and select Emissions
test via the function keys.
5. Carry out testing after a minimum of 60 seconds of
operation, measuring first at maximum load and then at
minimum load.
6. Flue gas values (for permissible values, see table)
Gas type
CO
Natural gas E/H/
7.8 - 9.8
LL
LPG (G31)
9.1 - 11.4
Max. base CO
value = 11.7 % (G20)
1)
2
2)
Max. base CO
value = 13.7 % (G31)
2
7. After the test has been completed, switch the appliance
off, remove the test probe and close the test port. Ensure
the screws and gasket are tight and firmly seated.
3064816_201804
32. Testing the combustion parameters
.
2
14/20/24 kW appliance
in %
O
in %
Lambda
2
2
3.5 - 7.0
1.35
1)
+/- 0.15
2)
and O
is required. Test the combustion parameters with
2
2
A
Fig.: Testing the flue gas parameters
B
63

Hide quick links:

Advertisement