System configuration 51
BMS burner output
• Burner is started subject to demand from the external
controller
• Internal appliance pump is enabled as a feed pump
from 2 V
• No temperature control
• Input E2:
0-10 V control from the external controller
0-2 V burner OFF
2-10 V burner output min. to max. within the programmed
limits (HG02 and HG04)
• Automatic output reduction when approaching TK
(HG22) is enabled. Shutdown when TK
System configuration 52
BMS set boiler water temperature
• Burner is started subject to demand from the boiler
thermostat
• Internal appliance pump is enabled as a feed pump from
2 V
• Boiler thermostat
• Input E2:
0-10 V control from the external controller
0-2 V burner OFF
2-10 V set boiler water temperature TK
(HG22)
• Max. set boiler water temperature = TK
(hysteresis)
System configuration 60
Cascade (automatic setting if cascade module is
connected)
• Burner starts following a demand from the cascade
module via eBUS (0-100 % burner output; min. to max.
within the programmed limits HG02 and HG04)
• Internal appliance pump is enabled as a feed pump
• Header temperature control via cascade module
• Input E2: not assigned
• Automatic output reduction when approaching TK
(HG22) is enabled. Shutdown when TK
• A low loss header or plate heat exchanger can be used to
provide hydraulic separation.
Important information:
In these schematic diagrams, shut-off valves, air vent valves and safety equipment are not fully shown. These
should be provided for each system individually, in line with the applicable standards and regulations.
Hydraulic and electrical data can be found in the hydraulic system solutions technical guide.
3064816_201804
24. Parameter description
max
is reached
max
(HG21) - TK
min
max
- 7 K
max
max
is reached
max
E2
BMS %
E2
BMS °C
E2
KM
SAF
49