Wolf CGS-2-14/120L Installation Instructions Manual page 30

Hide thumbs Also See for CGS-2-14/120L:
Table of Contents

Advertisement

230 V mains connection
The control and safety devices are fully wired and tested.
You only need to connect the power supply and the external
accessories.
Create a permanent connection for the power supply.
Provide the power supply via an omnipolar isolator (e.g.
heating system emergency stop switch) with at least 3 mm
contact separation.
No other consumers may be connected to the power cable.
In rooms with a bathtub or shower, the appliance may only be
connected via an RCD.
Installation information, electrical connection
- Isolate the system from the power supply before opening.
- Check that the appliance is isolated from the power supply.
- Swivel the control unit cover to one side.
- Remove the front casing.
- Open the lower casing cover of the HCM-2.
- Flexible power cable, at least 3x1.0 mm
70 mm of insulation)
- Remove the insert from the HCM-2 casing.
- Push the cable through the strain relief (insert) and secure.
- Pull out the Rast5 plug.
- Terminate the appropriate cores at the Rast5 plug.
- Push the inserts back into the HCM-2 casing.
- Push the Rast5 plug back into its correct position.
Connecting output Z1 (230 V AC; max. 1.5 A) *
Insert and secure the power cable through the cable gland.
Connect the power cable to terminals L1, N and
* Max. 1.5 A / 345 VA per output; sum of all outputs no more
than 600 VA
30
15. Electrical connection
Fig.: Mains connection
(strip approx.
2
.
Fig.: Connecting output Z1
3064816_201804