Modifications must only the carried out by a
NB
recognised heating contractor or by the Wolf
customer service to prevent a risk of injury,
equipment damage and incorrect functions.
If parameter A 09 (frost protection limit) is set lower than the factory setting, frost protection is no longer ensu-
red. This can lead to heating system damage.
The settings in column 1 apply to control accessories ART, AWT.
The settings in column 2 apply to Wolf control systems with programming module BM.
1
2
Parameters
GB 01
HG 01
Burner switching differential
HG 02 Min. modulation current HTG / DHW
Min. modulation current of the gas valve for HTG / DHW
HG 03 Max. modulation current DHW
Max. modulation current of the gas valve for DHW
GB 04 HG 04 Max. modulation current HTG
Max. modulation current of the gas valve for HTG
GB 06 HG 06 Pump operating mode
0 > Pump ON in winter mode
1 > Pump ON during burner operation
GB 07 HG 07 Pump run-on time HTG
Heating circuit pump run-on time in minutes in htg. mode
GB 08 HG 08 Max. flow temperature
Applicable to heating operation
GB 09 HG 09 Cycle block
Applicable to heating operation
HG 11 DHW quick start temperature
Temp. of the plate-type heat exchanger in summer mode
HG 12 Gas type
1 > NG (natural gas)
0 > LPG (LPG)
GB 05
A 09
Frost protection limit
with connected outside temperature sensor and
insufficient temperature > pump ON
HG 21 Min. flow temperature for heating operation
3062087_1108

Displaying / modifying control parameters

Unit
Factory
Min
set..
K
8
5
%
1
1
%
100
1
%
100
1
-
0
0
min
1
0
°C
80
40
min
7
1
°C
10
10
-
1
0
°C
2
-20
°C
40
20
Max
25
100
100
100
1
30
90
30
60
1
10
60
17