Wolf CGS-2-14/120L Installation Instructions Manual page 47

Hide thumbs Also See for CGS-2-14/120L:
Table of Contents

Advertisement

Parameter HG33
Burner hysteresis runtime
Factory setting: See table
Setting range: 1 to 30 min
Individual setting:_____
Parameter HG34
eBUS feed
Factory setting: See table
Setting range: OFF to ON
Individual setting:_____
Parameter HG37
Type of pump control
Factory setting: See table
Individual setting:_____
Parameter HG38
Set spread, dT pump control
Factory setting: See table
Setting range: 0 to 40 °C
Individual setting:_____
Parameter HG39
Soft start time
Factory setting: See table
Setting range: 0 to 10 min
Individual setting:_____
Parameter HG40
System configuration
3064816_201804
24. Parameter description
When the burner starts or when the boiler switches to heating mode, the burner
hysteresis is set to the parameter "Burner switching differential" HG01. Based on
this set value, the burner hysteresis within the set "Runtime burner hysteresis"
HG33 is reduced to the minimum burner hysteresis of HG60. This is designed
to prevent short burner runtimes.
In the "Auto" setting, the power supply to the eBUS system is switched on or
off automatically by the control unit, depending on the number of available
eBUS subscribers.
OFF = BUS feed is always off.
ON
= BUS feed is always on.
Auto = The control unit switches the BUS feed on or off automatically.
For setting the type of pump speed control in heating mode, cascade operation
and with BMS.
Constant = Fixed pump speed (HG17)
Linear
= Linear speed control between HG16 and HG17 corresponding to
the current burner output
dT
= Speed control between HG16 and HG17 to achieve the flow/return
temperature spread (HG38)
The set spread specified in HG38 applies if dT pump control is enabled in pa-
rameter HG37. The change to the pump speed means the spread is regulated
between flow and return within the speed limits in HG16 and HG17.
In heating mode, the burner is run at a lower output for the set time after burner
start.
The condensing boiler is fine-tuned to the heating system by selecting from 7
programmed system configurations that can only be checked and set directly
on the boiler under parameter HG40 using the AM display module or BM-2
programming unit. This parameter affects the function of the internal appliance
pump, input E2 and output A1.