Eaton AA13P Instruction Leaflet page 3

Size 1 or 2 type a thermal overload relay, 3 pole, ambient compensated or non-compensated

Advertisement

Size 1 or 2 Type A Thermal Overload Relay, 3 Pole,
Ambient Compensated or Non-Compensated
Heaters
Heaters are not included with the overload relay and must be
ordered separately per the heater selection table and the Information
listed below. When installing heaters be sure that connecting
surfaces are clean and heaters are attached securely to the relay
in the proper location with the screws provided. The trip rating of a
heater in a 40oC Ambient is 125% of the minimum full load current
shown in Table 5 or 6. When tested at 600 percent of its trip rating,
the relay will trip in 20 seconds or less (class 20).
The heaters should be selected on the basis of the actual full load
current and service factor as shown on the motor nameplate or in
the manufacturer's published literature. When the service factor of
the motor is 1.15 to 1.25, select heaters from the heater application
table. If the service factor of the motor is 1.0, or there is no service
factor shown, or a maximum of 115% protection is desired, select
one size smaller heater than indicated. When motor and overload
relay are in different ambient and when using non-compensated
overload relays, select heaters from the table using adjusted motor
currents as follows: decrease rated motor current 1% for each oC
motor ambient exceeds controller ambient. Increase rated motor
current 1 % for each oC controller ambient exceeds motor ambient.
For ambient compensated overload relays no adjustment in heater
selection is necessary for normal variations in ambient temperatures.
Short Circuit Protection
The relay will provide protection against abnormal load conditions to
current values exceeding normal locked rotor current; however, to
protect the relay from short circuit currents, branch circuit protection
must be provided per the National Electric Code. Protective device
ratings should not exceed the maximum values listed in the heater
application table. The relays, as protected are suitable for use on a
circuit capable of delivering not more than 5000 rms symmetrical
amperes.
Maintenance
Other than the normal tightening of all wire and heater connections,
no maintenance should be attempted on the unit. Complete replace-
ment of the unit must be made in the event of damage.
Medium-Voltage applications
The Type A OLR is used with current transformers and the "G" family
of heaters for coordination with mediumvoltage fuses. Since the
current transformers have a limited current output under short-circuit
conditions, no shortcircuit protection is required in their secondary
circuits supplying current to the Type "G" heaters. Wire the second-
ary circuits of the current transformers with #12 or #14 conductors.
Divide the motor full-load current by the transformer turns ratio to
determine the equivalent motor fullload current and select the appro-
priate heater from Table 5 for a service factor 1.15 medium-voltage
motor.
Table 5. Type G heaters
Code
Marking
Heater Rating
G22
2.03A
G23
2.23A
G24
2.44A
G25
2.69A
G26
2.95A
G27
3.23A
G28
3.55A
G29
3.90A
G30
4.28A
G31
4.67A
G32
5.10A
G33
5.50A
G34
6.10A
Equivalent
Full-Load Current
1.63-1.78 Amperes
1.79-1.95 Amperes
1.96-2.15 Amperes
2.16-2.35 Amperes
2.36-2.58 Amperes
2.59-2.83 Amperes
2.84-3.11 Amperes
3.12-3.42 Amperes
3.43-3.73 Amperes
3.74-4.07 Amperes
4.08-4.39 Amperes
4.40-4.87 Amperes
4.88-5.30 Amperes
Table 6. F series heater selection
For compensated OLR's in any size enclosure, and non-compensated OLR's in
enclosures with volume not less than 5500 cu. in. Wire with 75oC wire.
For use on one pole OLR's
Code
Full Load Current of Motor
Marking
(Amperes) (40oC Ambient)
FH03
.25 - .27
FH04
.28 - .31
FH05
.32 - .34
FH06
.35 - .38
FH07
.39 - .42
FH08
.43 - .46
FH09
.47 - .50
FH10
.51 - .55
FH11
.56 - .62
FH12
.63 - .68
FH13
.69 - .75
FH14
.76 - .83
FH15
.84 - .91
FH16
.92 - 1.00
FH17
1.01 - 1.11
FH18
1.12 - 1.22
FH19
1.23 - 1.34
FH20
1.35 - 1.47
FH21
1.48 - 1.62
FH22
1.63 - 1.78
FH23
1.79 - 1.95
FH24
1.96 - 2.15
FH25
2.16 - 2.35
FH26
2.36 - 2.58
FH27
2.59 - 2.83
FH28
2.84 - 3.11
FH29
3.12 - 3.42
FH30
3.43 - 3.73
FH31
3.74 - 4.07
FH32
4.08 - 4.39
FH33
4.40 - 4.87
FH34
4.88 - 5.3
FH35
5.4 - 5.9
FH36
6.0 - 6.4
FH37
6.5 - 7.1
FH38
7.2 - 7.8
FH39
7.9 - 8.5
FH40
8.6 - 9.4
FH41
9.5 - 10.3
FH42
10.4 - 11.3
FH43
11.4 - 12.4
FH44
12.5 - 13.5
FH45
13.6 - 14.9
FH46
15.0 - 16.3
FH47
16.4 - 18.0
FH48
18.1 - 19.8
FH49
19.9 - 21.7
FH50
21.8 - 23.9
FH51
24.0 - 26.2
Above heaters for use on size 1
FH52
26.3 - 28.7
28.8 - 31.4
FH53
31.5 - 34.5
FH54
34.6 - 37.9
FHSS
38.0 - 41.5
FH56
41.6 - 45.0
FH57
Above heaters for use on size 2
mWARNING:
TO PROVIDE CONTINUED PROTECTION AGAINST FIRE AND SHOCK HAZ-
ARD, THE COMPLETE OVERLOAD RELAY MUST BE REPLACED IF BURNOUT
OF A CURRENT ELEMENT OCCURS. SEE TABLE I.
Instruction Leaflet IL14568
Effective June 2020
Max. Protect.
Load
Device
Wire
(Amp)
Size
1A
#14
1A
#14
1A
#14
1A
#14
1A
#14
2A
#14
2A
#14
2A
#14
3A
#14
3A
#14
3A
#14
3A
#14
3A
#14
3A
#14
3A
#14
3A
#14
5A
#14
6A
#14
6A
#14
6A
#14
6A
#14
6A
#14
10A
#14
10A
#14
10A
#14
15A
#14
15A
#14
15A
#14
15A
#14
15A
#14
15A
#14
20A
#14
20A
#14
20A
#14
25A
#14
25A
#14
30A
#14
30A
#14
35A
#14
35A
#14
40A
#14
45A
#14
45A
#14
50A
#12
60A
#12
60A
#12
70A
#10
80A
#10
80A
#10
90
#8
100
#8
125
#8
125
#8
125
#6
150
#6
EATON www.eaton.com
3