Alarm ID
Alarm
Name
2067
Faulty
Power
Collector
2072
Transient
AC
Overvolta
ge
Issue 06 (2020-10-23)
Alarm
Possible Cause
Severity
Major
Cause ID = 1
Power meter disconnection.
Major
Cause ID = 1
The inverter detects that
the phase voltage exceeds
the transient AC
overvoltage protection
threshold.
NO TE
Contact your dealer or Huawei technical support if the measures listed in the
Troubleshooting Suggestion column have been taken but the fault persists.
Copyright © Huawei Technologies Co., Ltd.
7 Maintenance
Troubleshooting Suggestion
1. Check that the preset power
meter model is the same as
the actual model.
2. Check that the preset
communications parameters
for the power meter are the
same as the actual
configurations.
3. Check that the power meter
is powered on and the RS485
communications cable is
connected.
1. Check whether the grid
connection voltage exceeds
the upper threshold. If yes,
contact the local power
operator.
2. If you have confirmed that
the grid connection voltage
exceeds the upper threshold
and obtained the consent of
the local power operator,
modify the overvoltage
protection threshold.
3. Check that the peak grid
voltage does not exceed the
upper threshold.
77