Fan Control; Indoor Fan Control - Fujitsu ABYG36KRTA Service Manual

Ceiling type
Hide thumbs Also See for ABYG36KRTA:
Table of Contents

Advertisement

3. Fan control

Tr: Room temperature
Ts: Setting temperature

3-1. Indoor fan control

¢ Fan speed
Indoor fan speed is defined as below.
Operation mode
Heating
Cooling/Fan
*1: Fan mode only
*2: Cooling mode only
¢ Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
¢ Cooling operation
Switch the airflow AUTO, and indoor fan motor will run according to room temperature, as below.
On the other hand, if switched in HIGH—QUIET, indoor motor will run at a constant airflow of COOL
operation modes QUIET, LOW, MED, HIGH as shown in "Fan speed" above.
Airflow change over (Cooling: Auto)
2°C
3-1. Indoor fan control
Fan mode
HIGH
MED+
MED
LOW-
QUIET
Cool air prevention
S-LOW
HIGH
MED
LOW
QUIET
Soft quiet
S-LOW
Dry
Tr - Ts ≥
2°C
> Tr - Ts ≥
1°C
1°C > Tr - Ts
When room
temperature drops
ABYG36KRTA
1,090
1,020
920
830
700
500
300
1,120
920
830
700
1
500*
2
300*
X zone: 700
J zone: 700
Tr - Ts ≥
HIGH mode
2.5°C
MED mode
1.5°C > Tr - Ts
LOW mode
When room
temperature rises
- (04-9) -
Speed (rpm)
ABYG45KRTA
1,120
1,030
940
870
740
500
300
1,140
940
870
740
1
500*
2
300*
X zone: 740
J zone: 740
2.5°C
> Tr - Ts ≥
1.5°C
3. Fan control

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Abyg45krtaAoyg36krtaAoyg45krta

Table of Contents