¢ Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the "Peak cut mode" when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
• Circuit diagram example
Outdoor unit
control PCB
Connector
1
2
1
2
Input signal
Peak cut mode
• Optional part
Part name
External connect kit
4-1. External input
Connected unit
(Locally purchased)
Example: Switch
10m*
Signal
On
Off
On
Off
Model name
UTY-XWZXZ3
- (05-22) -
Contact capacity: DC 24 V or more, 10 mA
or more.
*: Make the distance from the PCB to the
connected unit within 10 m.
Construct a circuit as shown in this figure
with using optional parts mentioned below.
Input signal: On in "Peak cut mode"
Input signal: Off in normal operation
To set the level of "Peak cut mode", refer
to
"Peak cut mode"
External input wire
on page 05-9.
Exterior
4. External input and output for outdoor unit