Fujitsu ABYG36KRTA Service Manual page 110

Ceiling type
Hide thumbs Also See for ABYG36KRTA:
Table of Contents

Advertisement

¢ Model: AOYG45KRTA
Compressor frequency soon after starting is controlled as below.
Frequency X
Frequency IX
Frequency VIII
Frequency VII
Frequency VI
Frequency V
Frequency IV
Frequency III
Frequency II
Frequency I
Time 1
• Normal operation
I
Frequency
(rps)
41
1
Time (sec)
60
• Special operation
I
Frequency
(rps)
41
1
Time (sec)
120
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– When the compressor starts for the first time since the breaker turns on
1-4. Compressor frequency at normal start-up
Time 2
Time 3
Time 4
II
III
IV
46
51
57
2
3
4
120
180
240
II
III
IV
46
51
57
2
3
4
185
245
305
- (04-4) -
Time 5
Time 6
Time 7
V
VI
VII
60
72
81
5
6
7
360
420
480
V
VI
VII
60
72
81
5
6
7
605
665
725
Time 8
Time 9
Time 10
VIII
IX
X
91
100
110
8
9
10
540
600
660
VIII
IX
X
91
100
110
8
9
10
785
845
1,000
1. Compressor frequency control