Check point 4. Check serial signal (Reverse transfer signal)
Check serial signal (Reverse transfer signal)
Check if indicated value swings between AC 90 V and AC 270 V at the outdoor unit terminal 1
—3.
If it is abnormal, check the parts below.
Outdoor unit fan motor in
If outdoor fan motor is abnormal, replace outdoor unit fan motor and main PCB.
If the checked parts are normal, replace the main PCB.
Check point 1-2. Check external cause such as noise
Check the complete insulation of the grounding.
Check if there is any equipment that causes harmonic wave near the power cable (Neon light
bulb or any electronic equipment which causes harmonic wave).
2-1. E: 11. Serial communication error (Serial reverse transfer error) (Outdoor unit)