• Heating mode
Model name
AOYG36KRTA
AOYG45KRTA
1-5. Compressor frequency limitation by outdoor temperature
I zone
20°C
H zone
16°C
G zone
12°C
F zone
7°C
E zone
2°C
D zone
-7°C
C zone
-10°C
B zone
-15°C
A zone
Outdoor temperature zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
I zone
A zone
B zone
C zone
D zone
E zone
F zone
G zone
H zone
I zone
- (04-6) -
Limitation of compressor
frequency
58 rps
52 rps
43 rps
38 rps
28 rps
23 rps
20 rps
17 rps
17 rps
46 rps
42 rps
35 rps
32 rps
23 rps
20 rps
17 rps
13 rps
16 rps
1. Compressor frequency control