Indoor Fan Control - Fujitsu AB A30LBT Series Service Instruction

Hide thumbs Also See for AB A30LBT Series:
Table of Contents

Advertisement

1-5. INDOOR FAN CONTROL

1. Fan speed
( Table 5 : Indoor Fan Speed )
AU*A30/36LBLU
Operation mode
Cooling
Heating
Dry
Monitoring
AB*A30/36LBT
Operation mode
Cooling / Heating
Dry
Monitoring
2. FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QU, LOW, MED, HIGH, while the indoor
fan only runs.
When [AUTO] is selected, the indoor fan motor runs continuously [MED] mode.
3. COOLING OPERATION
Switch the airflow [AUTO], and the indoor fan motor will run according to a room temperature,
as shown in Figure 6.
On the other hand, if switched in [HIGH]
operation modes QU, LOW, MED, HIGH,as shown in Table 5.
( Fig.6 : Airflow change - over ( Cooling : AUTO ) )
TR-Ts > 2 °C
=
2 °C > TR-Ts > 1 °C
=
1 °C > TR-Ts
When the room
temperature drops
Air flow mode
Speed (rpm)
Hi
650
Me
550
Lo
500
Qu
400
Hi
650
Me+
600
Me
550
Lo
500
Qu
400
Cool Air Prevention
350
Auto
400
S-Lo
250
Air flow mode
Speed (rpm)
Hi
830
Me
700
Lo
600
Qu
550
Auto
400
S-Lo
250
[QU], the indoor motor will run at a constant airflow of [COOL]
HIGH mode
MED mode
LOW mode
When the room
temperature rises
AR*A30/36LBTU
Operation mode
Cooling
Heating
Dry
Monitoring
TR-Ts > 2.5 °C
=
2.5 °C > TR-Ts > 1.5 °C
=
1.5 °C > TR-Ts
01-05
Air flow mode
Speed (rpm)
Hi
1200
Me
1000
Lo
830
Qu
650
Hi
1200
Me+
1100
Me
1000
Lo
830
Qu
650
Cool Air Prevention
500
Auto
650
S-Lo
250
TR : Room temperature
Ts : Setting temperature