Digital electronic refrigeration units controller
Table of Contents

Advertisement

X34-X34S
DIGITAL ELECTRONIC
REFRIGERATION UNITS
CONTROLLER
OPERATING INSTRUCTIONS
18/05 - cod.: ISTR_M_X34_E_05_--
ASCON TECNOLOGIC S.r.l.
Viale Indipendenza 56, 27029 - VIGEVANO (PV) ITALY
Tel.: +39 0381 69871 - Fax: +39 0381 698730
http:\\www.ascontecnologic.com
info@ascontecnologic.com
PREFACE
This manual contains the information necessary for
m
the product to be installed correctly and also instruc-
tions for its maintenance and use; we therefore
rEcommend that the utmost attention is paid to the
following instructions and to save it.
This document is the exclusive property of Ascon Tecnologic
S.r.l. which forbids any reproduction and divulgation, even
partially, of the document, unless expressly authorized.
Ascon Tecnologic S.r.l. reserves the right to make any formal
or functional changes at any moment and without any notice.
Ascon Tecnologic S.r.l. and its legal representatives do not
assume any responsibility for any damage to people, things
or animals deriving from violation, wrong or improper use or
in any case not in compliance with the instrument features.
Whenever a failure or a malfunction of the device
m
may cause dangerous situations for persons, thing
or animals, please remember that the plant has to be
equipped with additional electromechanical devices
which will guarantee safety.
Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 1
Index
1. Instrument description ............................................... 2
1.1
General description ........................................................... 2
1.2
Front panel description ..................................................... 2
2. Programming ............................................................... 3
2.1
Fast Set Point programming .............................................. 3
2.2
Standard mode parameters programming ........................ 3
2.3
2.4
(parameters programming level) ....................................... 3
2.5
Reset parameters to default value .................................... 4
2.6
Keyboard lock function ...................................................... 4
2.7
Setting the current time and date ...................................... 4
2.8
Scheduling events at defined times .................................. 5
2.9
Displaying HACCP alarms ................................................ 5
3. Usage Warnings .......................................................... 6
3.1
Admitted usage ................................................................. 6
4. Installation warnings ................................................... 6
4.1
Mechanical mounting ........................................................ 6
4.1.1
Mechanical dimensions [mm] ............................................... 6
4.1.2
Panel cut-out ......................................................................... 6
4.1.3
Mounting ............................................................................... 6
4.2
Electrical connections ....................................................... 7
4.2.1
Electrical wiring diagram ....................................................... 7
5. Functions ..................................................................... 7
5.1
ON/Stand-by function ........................................................ 7
5.2
Normal, "Eco" and Turbo operating modes ....................... 7
5.4
Digital Inputs ..................................................................... 9
5.5
Outputs and buzzer configuration ................................... 10
5.6
Temperature control ........................................................ 10
5.7
5.8
Defrost control ................................................................. 12
5.8.1
Starting automatic defrosts ................................................. 12
5.8.2
Manual defrost .................................................................... 13
5.8.3
Defrost ends ....................................................................... 13
5.8.4
5.8.5
Defrost display lock ............................................................. 14
5.8.6
Hot-gas defrost in centralized systems ............................... 14
5.9
Evaporator fans control ................................................... 15
5.10 Alarm functions ............................................................... 16
5.10.1 Temperature alarms ............................................................ 16
5.10.2 External alarms (digital inputs) ........................................... 17
5.10.3 Open door alarm................................................................. 17
5.11 HACCP function (alarm recording) ................................. 17
5.11.1 HACCP temperature alarms ............................................... 18
5.11.2 HACCP power failure alarms .............................................. 18
5.11.3 HACCP alarms from digital input ........................................ 18
5.13 Clock programmable events ............................................ 19
5.14 RS485 Serial Intefarce .................................................... 19
6. Accessories ............................................................... 20
6.1
6.2
TVR Y remote display ..................................................... 20
7. Programmable parameters table .............................. 21
8. Problems and maintenance ...................................... 26
8.1
Notifications .................................................................... 26
8.1.1
Error messages .................................................................. 26
8.1.2
Other messages ................................................................. 26
8.2
Cleaning .......................................................................... 26
8.3
Disposal .......................................................................... 26
9. Warranty and Repairs ............................................... 26
10. Technical data ............................................................ 26
10.1 Electrical characteristics ................................................. 26
10.2 Mechanical characteristics .............................................. 27
10.3 Functional features ......................................................... 27
11. How to order .............................................................. 27
/Aux ................................ 18

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the X34 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ascon tecnologic X34

  • Page 1: Table Of Contents

    9. Warranty and Repairs ..........26 10. Technical data ............26 10.1 Electrical characteristics ..........26 10.2 Mechanical characteristics ..........27 10.3 Functional features ............27 11. How to order .............. 27 Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 1...
  • Page 2: Instrument Description

    (clock chip not working). If flashing rapidly, it means the clock battery is drained 13. LED Stand-By: When the instrument is in Stand-by mode is the only lit LED. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 2...
  • Page 3: Programming

    – Enter the programming mode using the t. P P Password, keys. select the parameter that must be accessible with no pass- – Once the desired value has been set, press the key word protection. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 3...
  • Page 4: Reset Parameters To Default Value

    When in this condition, pressing any key cancels the failure indication and the LED returns to solid (on and not flashing). Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 4...
  • Page 5: Scheduling Events At Defined Times

    14 x 7 = 98 weekly events to be scheduled (using d. 8). AL.ENDURANCE AL.ENDURANCE Hi/Lo TEMP. PEAK For the event types that can be programmed, see the rel- (min) evant paragraph. e. 0 5 12. 5 Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 5...
  • Page 6: Usage Warnings

    +0.6 Connect the instrument as far away as possible from sourc- es of electromagnetic disturbances such as motors, power relays, relays, solenoid valves, etc. 4.1.3 Mounting “Butterfly” brackets Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 6...
  • Page 7: Electrical Connections

    2 (1) A 2 A Gen.Use t. 6 (switch to Eco mode) and t. 7 (switch to Normal mode). For further information see the paragraph on programming events through the clock. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 7...
  • Page 8 However, Turbo mode is ap- but it is also possible to assign it temperature alarms plied automatically to restore product temperature at the end (possible usages: product, antifreeze probe, etc.); of Eco mode. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 8...
  • Page 9: Digital Inputs

    S parameter. tion are defined by parameters i. 1 F and i. 2 F and whose 14 External HP alarm notified and ot output deactivated by Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 9...
  • Page 10: Outputs And Buzzer Configuration

    F o and the function is conditioned by the time set at parameter o. t u. The parameter o. F o can be configured for: oF Auxiliary output not active; Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 10...
  • Page 11: Compressor Protection Function And Power-On Delay

    Remember that the operation of the temperature controller can be conditioned by the following functions: Compressor protection function and power-ON delay, Defrost, Open door and External alarm with output disable. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 11...
  • Page 12: Defrost Control

    (d . d i or d . S d if is the first defrost), anticipating, when d. 4 Thursday; necessary, the defrost execution, all based on an algorithm d. 5 Friday; Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 12...
  • Page 13: Manual Defrost

    The defrost ends after the d. d E programmed time. During defrost the dF output switches ON/OFF to con- trol evaporator temperature in heating mode with d. t E Set Point and 1° differential (Hysteresis). Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 13...
  • Page 14: Defrosts In Event Of Evaporator Probe Error

    2 = oF in order to avoid Similarly while defrosting, the Liquid solenoid valve (the unwanted influences on total defrost duration. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 14...
  • Page 15: Evaporator Fans Control

    Otherwise, the defrost request happens during the P . P 2 time The parameter F. F E instead decides whether the fans must count, the Suction valve and the fans deactivation occurs at Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 15...
  • Page 16: Alarm Functions

    Au (e.g. antifreeze function) or as CD (e.g. dirty condenser function). Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 16...
  • Page 17: External Alarms (Digital Inputs)

    Similarly the value of the H. d L parameter can be reset by are immediately reactivated (fans or fans + compressor). holding down the key for more than 5 seconds while the value is displayed. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 17...
  • Page 18: Haccp Temperature Alarms

    3 Pressing the key for at least 1 s, it is possible to switch display shows “---”). the instrument from ON to Stand-by status and vice-ver- sa. If switch-ON/Stand-by events are programmed using Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 18...
  • Page 19: Clock Programmable Events

    Serial interface baud rate. Settings available: the next event that switches it to Eco mode. 1 = 9600 baud, 2 - 19200 baud, 3 - 38400 baud. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 19...
  • Page 20: Accessories

    Pr1 through a 2½ digit display. Power supply Cable 10 m max. TVR Y (--) For additional info, please look at the TVR Y instruction manual. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 20...
  • Page 21: Programmable Parameters Table

    Function and function logic of digital input Pr4 i. 4 F oF No function Delay to Eco mode with door closed i. E t 0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10) Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 21...
  • Page 22 0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) H Heating C Cooling Output operating mode nr Neutral Zone r. H C HC Neutral Zone with independent Set point C3 Cooling with 3 automatic switch modes Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 22...
  • Page 23 0.01 ÷ 9.59 (min.s) ÷ 99.5 (min.s x 10) oF Power ON dealy disabled Temperature Alarms 2 delay at power on 2.00 A. P 2 0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10) Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 23...
  • Page 24 HACCP Alarms Parameters level Visible as unprotected parameters MODBUS Station address (for serial communication) 1 ÷ 255 t. A S 9600 Serial communication baud rate 19200 t. b r 38400 Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 24...
  • Page 25 H. 0 9 (#) Stored Alarm no. 9 H. 1 0 (#) Stored Alarm no. 10 H. 0 9 (#) Number of HACCP alarms deleted (out of space) 0 ÷ 100 Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 25...
  • Page 26: Problems And Maintenance

    Reinforced insulation between the low voltage section (type with the local standards in force on H supply type and relay outputs) and the extra low voltage waste disposal. section (inputs), Reinforoced between power supply and relay outputs. Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 26...
  • Page 27: Mechanical Characteristics

    EN61000-4-5: supply 2kV com. mode, 1 kV\diff. mode; EN61000-4-6: 3V), Directive 2006/95/CE (EN 60730-1, EN 60730-2-9), Control 37/2005/CE (EN13485 air, S, A, 2, -50°C +90°C with probe NTC 103AT11 or Pt1000 clas B or better). Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 27...
  • Page 28 Ascon Tecnologic - X34 - OPERATING INSTRUCTIONS - PAG. 28...