Xylem LOWARA e-SVE Installation, Operation And Maintenance Manual page 27

Smart pump range
Table of Contents

Advertisement

Figure 16: Connection label
Table 11: I/O terminals
Item
Fault Signal
Auxiliary Voltage Supply
Analog 0-10V
External Pressure sensor
[also Differential]
External Start/Stop
External Lack of Water
Communication Bus
Communication Bus
Terminals
Number
Description
C
4
No
5
15V
6
Voltage Supply
P2IN/S+
7
Actual value voltage
Ground for external sensor or
P2C/S-
8
external speed control
P1+
9
Voltage Supply
P1-
10
Actual value current
START
11
External ON/OFF input
Ground for external ON/OFF
STOP
12
input
LOW+
13
External Lack of Water
Ground for External Lack of
LOW-
14
Water
B1
15
RS485 port 1: RS485 -1N
A1
16
RS485 port 1: RS485 -1P
GND
17
GND, electronic ground
B2
18
RS485 port 2: RS485 -2N
A2
19
RS485 port 2: RS485 -2P
GND
20
GND, electronic ground
en – Original instructions
Comments
In case of Power Wires: use
M20 cable gland
15VDC, Ʃ max. 100mA
0÷10 VDC
GND, electronic ground (for
S+)
15VDC, Ʃ max. 100mA
4÷20 mA
Default short circuited.
Pump is enabled to RUN
Default short circuited.
Lack of Water Detection:
enabled
ACT, HCS control mode:
RS 485 port1 for external
communication
MSE, MSY control mode:
RS 485 port1 for multi-pump
systems
RS 485 port2 for external