Johnson Controls WRZ Series Installation Manual

Johnson Controls WRZ Series Installation Manual

Occupancy wireless room sensors
Hide thumbs Also See for WRZ Series:

Advertisement

Quick Links

Application
Use the occupancy sensing WRZ Series Wireless Room
Sensors to sense room or zone temperature and transmit
wireless temperature control data. The WRZ-MHN0100-2
model also senses and transmits relative humidity (RH).
All models include an onboard passive infrared (PIR)
occupancy sensor that detects motion to determine
the occupancy status of a space. This feature can help
provide up to 30% in energy savings in high-energy usage
environments such as schools, residence halls, offices,
and hospitals because it adjusts the temperature of the
space based on the occupancy status. In addition, the PIR
occupancy sensor facilitates trending of floor space usage
in these environments.
In ZFR18xx Wireless Field Bus Systems (ZFR181x, ZFR182x,
and ZFR183x) mesh applications, up to nine WRZ sensors
communicate with a single controller through the ZFR18xx
Router or ZFR Pro Series Router for multi-sensor averaging
or high and low temperature selection.
In wired Field Bus applications, the sensors communicate
over wireless through the WRZ-7860 Wireless Receiver.
The WRZ-7860 Receiver transfers data to the controller
through the Sensor Actuator (SA) communication bus.
In an application, one occupancy sensing WRZ Series
Sensor reports to one WRZ-7860 Receiver, but up to five
occupancy sensing WRZ Series Sensors can associate with
a single WRZ-7860 Receiver formulti-sensor averaging or
high and low temperature selection.
Models are available with or without an LCD. Depending
on the sensor model, the occupancy sensing WRZ
Series Sensor transmits sensed temperature, setpoint
temperature, sensed humidity, occupancy status, and low
battery conditions to an associated router or receiver. Use
the occupancy sensing WRZ Series Sensors for indoor,
intra-building applications only.
The occupancy sensing WRZ Series Sensors use direct-
sequence, spread-spectrum RF technology, and operate
on the 2.4 GHz Industrial, Scientific, and Medical (ISM)
band. The receiver meets the IEEE 802.15.4 standard for
low power, low duty cycle RF transmitting systems.
Occupancy Sensing WRZ Series Wireless Room
Sensors Installation Guide
Important: The WRZ Series Sensors are intended
to provide an input to equipment under normal
operating conditions. Where failure or malfunction of
the sensor could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the sensor.
Important: Le WRZ Series Sensors est destiné à
transmettre des données entrantes à un équipement
dans des conditions normales de fonctionnement.
Lorsqu'une défaillance ou un dysfonctionnement
du sensor risque de provoquer des blessures
ou d'endommager l'équipement contrôlé ou un
autre équipement, la conception du système de
contrôle doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que
des systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du sensor.
North American emissions
compliance
United States
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1.
This device may not cause harmful interference, and
2.
This device must accept any interference received,
including interference that may cause undesired
operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by the
party responsible for compliance could void the user's
authority to operate the equipment.
Canada
Industry Canada Statement(s)
The term IC before the certification/registration number
only signifies that the Industry Canada technical
specifications were met.
Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est
conforme aux spécifications techniques d'Industry
Canada.
Part No. 24-10332-96 Rev. F
2020-07-09
*241033296F*
WRZ-MHN0100-2, WRZ-MTJ0100-0

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls WRZ Series

  • Page 1 2020-07-09 Application Important: The WRZ Series Sensors are intended Use the occupancy sensing WRZ Series Wireless Room to provide an input to equipment under normal Sensors to sense room or zone temperature and transmit operating conditions. Where failure or malfunction of wireless temperature control data.
  • Page 2: Installation

    Other than battery replacement, the sensor is not user-serviceable. Parts included • One occupancy sensing WRZ Series Sensor with strips of double-sided adhesive foam tape installed • One DIP switch overlay for a mesh network application that uses a ZFR or ZFR Pro Series Router •...
  • Page 3 Remove the sensor housing from its mounting base. See Figure 3. Peel off the protective paper from the factory- installed strips of adhesive foam tape on the back of the mounting base. Occupancy Sensing WRZ Series Wireless Room Sensors Installation Guide...
  • Page 4 Important: Ensure that the PAN OFFSET is the same for each ZFR or ZFR Pro Series Coordinator, ZFR or ZFR Pro Series Router, and occupancy sensing WRZ Series Sensor in a mesh network. See Figure 7. Occupancy Sensing WRZ Series Wireless Room Sensors Installation Guide...
  • Page 5 Refer to the WRZ Series One- to-One Wireless Room Sensing System Technical Bulletin (LIT-12011641) for information about...
  • Page 6 3 times to indicate a strong signal, 2 times to indicate a good signal, or 1 time to indicate Note: For WRZ Series Sensors with an LCD display, a marginal signal. For sensors with an LCD display, a the humidity value may appear as 0.0% when the...
  • Page 7: Version Compatibility

    WRZ-SST-120 Wireless Sensing System Tool to One-to-one mode perform a site survey and test the wireless signal strength You can add up to five occupancy sensing WRZ Series between potential device locations. Before you install the Sensors to a WRZ-7860 Receiver in one-to-one mode.
  • Page 8 Sensor, to function as a site survey tool To check the battery strength of the occupancy sensing for the WRZ-7860 one-to-one room WRZ Series Sensor, press and hold the manual occupancy temperature sensing system, or for the override button. See Figure 1. If the battery level and...
  • Page 9: Technical Specifications

    Canada: Industry Canada IC: 5969A-MATRIXL or 279A-WRZRADIO Europe: CE Mark – Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the RED, EMC, LVD, and RoHS directives. Japan: Transmission complies with Article 38-24 paragraph 1 of the Radio Law...
  • Page 10: Product Warranty

    CHINA Contact information Contact your local branch office: www.johnsoncontrols.com/locations Contact Johnson Controls: www.johnsoncontrols.com/contact-us © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. www.johnsoncontrols.com...

This manual is also suitable for:

Wrz-mhn0100-2Wrz-mtj0100-0

Table of Contents