18
en | Programming
6

Programming

6.1

Supervisory zone

Several options are available to program the module's supervision point. Program the point
using a point index configured as:
Point Type 0 (24 h)
Pt Response 9
Buzz on Fault = 2
Fire = Yes
Program all other selections for the point index number No.
6.2

Alarm output

For instructions on programming the control panel, refer to the panel's Program Entry Guide.
For compatibility information about synchronization modules and strobes, refer to the panel's
Approved Applications Compliance Guide.
2020.05 | 04 | 4998122260
Short = Fire Supervision;
Open = Fire Trouble
Installation manual
Notification Appliance Circuit Module