8 Settings
"Installation settings" menu area
Setting options
Parameter
Description
Voltage high off
High Off
Voltage high on
High On
Disconnection time for voltage high off
High Off T
Voltage low off
Low Off
Voltage low on
Low On
Disconnection time for voltage high off
Low Off T
Voltage high off slowly
Hi Off Slow
Voltage high on slowly
Hi On Slow
Disconnection time for voltage high off slowly
Hi Off Sl T
Voltage low off slowly
Lo Off Slow
Voltage low on slowly
Lo On Slow
Disconnection time for voltage low off slowly
Lo Off Sl T
Menu item path
Main Menu > Install Settings > Grid Settings > Volt-
age Protection
Changing the settings
This procedure is the same for all parameters.
1 0 . N o v 2 0 1 9 1 5 : 3 2
S t a t u s :
O n G r i d
P o w e r :
E - T o d a y :
I n v e r t e r I n f o .
G e n e r a l S e t t i n g s
I n s t a l l S e t t i n g s
A c t i v e / R e a c t i v e P w r
F R T
W a r n i n g :
A d j . w o u l d a f f e c t
e n e r g y p r o d u c t i o n .
P a s s w o r d
0 * * *
I n v e r t e r I D :
I n s u l a t i o n
C o u n t r y
G r i d S e t t i n g s
86
1.
When the default information is displayed, press any button to open the main menu.
Otherwise, press the
0 W
0 k W h
2.
Use the
the
button.
ENT
3.
Enter the password provided by Delta customer service. Use the
to set the individual numerals.
Press the
ENT
1
4.
Use the
button.
ENT
Setting range
184.0 .. 276.0 V
184.0 .. 276.0 V
0.0 .. 5.0 s
184.0 .. 276.0 V
184.0 .. 276.0 V
0 .. 5.0 s
184.0 .. 276.0 V
184.0 .. 276.0 V
0 .. 600 s
184.0 .. 276.0 V
184.0 .. 276.0 V
0 .. 600 s
button repeatedly until the main menu is displayed.
ESC
and
buttons to select the Install Settings entry. and then press
button to confirm a numeral.
and
buttons to select the Grid Settings entry and then press the
Installation and Operation Manual for Power Inverter RPI M6A M8A M10A EU V4 EN 2020-07-13
and
buttons