6.5
Mounting the inverter and grounding
the inverter housing
DANGER
Electric shock
► Always observe the local regulations relating
to grounding cable requirements.
► To increase the safety of the system, always
ground the inverter housing even when this
is not required by the local regulations.
► Always ground the inverter housing before
connecting the inverter to the grid and solar
modules.
► Yellow/green copper cables with at least
6 mm
cable cross-section must normally be
2
used.
Installation and Operation Manual for Power Inverter RPI M6A M8A M10A EU V4 EN 2020-07-13

Mounting the inverter and grounding the inverter housing

1. Attach the mounting plate to the wall / the mounting sys-
tem with 8 M6 screws.
2. Hang the inverter onto the mounting plate.
3. Check that the inverter hangs correctly on the mounting
plate.