13 Technical Data
13.
Technical Data
Input (DC)
Maximum recommended PV power
Maximum output
Input voltage range
Maximum input voltage
Rated voltage
Switch-on voltage
Switch-on power
MPP operating voltage range
MPP operating voltage range at full power
Symmetrical load
Asymmetrical load (60/40%)
Maximum input current, total (DC1/DC2)
Maximum short-circuit current in the event of
failure
Number of MPP trackers
Maximum asymmetry
Number of DC inputs, total (DC1/DC2)
Galvanic isolation
Overvoltage category
2)
Output (AC)
Max. Apparent power
3)
Rated apparent power
Voltage range
5)
Rated current
Maximum current
Switch-on current
Rated frequency
Frequency range
5)
Adjustable power factor
Total harmonic distortion
DC power supply
Power loss in night mode
Overvoltage category
2)
142
RPI M6A
7500 W
1)
P
6600 W
200 to 1000 V
1000 V
DC
600 V
DC
>250 V
DC
40 W
200 to 1000 V
315 to 800 V
425 to 800 V
20 A (10 A/10 A)
13 A/13 A
Parallel inputs: 1 MPP tracker, separate inputs: 2 MPP trackers
60/40%
2 (1/1)
No
II
RPI M6A
6300 VA
6000 VA
4)
230 ± 20%/400 V
8.7 A
9.7 A
31 A/100 µs
50/60 Hz
50 ± 5 Hz/60 ± 5 Hz
0.8 cap to 0.8 ind
< 3%
< 0.5% rated current
< 2 W
III
RPI M8A
10000 W
P
8800 W
DC
DC
415 to 800 V
DC
565 to 800 V
DC
20 A (10 A/10 A)
13 A/13 A
2 (1/1)
RPI M8A
8400 VA
8000 VA
± 20%; 3-phase + PE or 3-phase + N + PE
AC
11.6 A
13 A
Installation and Operation Manual for Power Inverter RPI M6A M8A M10A EU V4 EN 2020-07-13
RPI M10A
12500 W
P
11,000 W
415 to 800 V
DC
415 to 800 V
DC
25 A (15 A/10 A)
19.5 A/13 A
3 (2/1)
RPI M10A
10500 VA
10000 VA
14.5 A
16 A
DC
DC