Air intake filter clean (The filter should be customized).

Air intake filter should be customized as one individual packing, which is installed in site.
Step 1: Dismantle the air filter.
Twist of screws and get out the plate.
Pull out the filter along the supporting slot.
Step 2: Clean the air filter.
Vacuum cleaner or fresh water may be used to clean the air filter. If the dust accumulated
too much, please use soft brush and mild detergent to clean.
The air-in side should face up when using vacuum cleaner.
The air-in side should face down when using water.
After cleaning, please dry out in cool place. Do not dry out the air filter under direct sunshine
or heat.
Step 3: Re-install the air filter.
Condenser coil
Unfiltered air circulates through the unit's condenser coil can cause the coil's surface to become
clogged with dust. Clean the coil, vertically (i.e., with the fins), and stroke the coil surface with a soft
brush. Be sure to keep all vegetation away from the condenser coil area.
Periodic maintenance
To keep the unit operating safety and efficiently, the entire system should be checked at least once