Rooftop package
Table of Contents

Advertisement

MCAC-RTT6S-201701
Any reduction of the unit clearances indicated in these pictures may result in condenser coil
starvation or the recirculation of warm condenser air. Actual clearances which appear to be
inadequate should be reviewed.

3. Lifting

Rigging cables should have adequate capability to resist 3 times weight of unit. Before lift,
please check and ensure that hooks are holding tightly to unit and lifting angles are no less than
.
60°
Cloth material or hard-paper should be padded in the contact place between unit and rigging
cable. Rigging cable should be entwined a round at the hook for prevent danger by cable slip
because of weight unbalance.
During lifting, anyone forbidden lingering under the lifting unit.
Midea R410A Tropical ClimaCreator Series Rooftop Package 220V 3Ph 60Hz