Val Controls IDC24-A User Manual page 51

Intelligent diagnostic controller
Hide thumbs Also See for IDC24-A:
Table of Contents

Advertisement

No. 464
FST error: Timeout during FST
Description
The valve did not reach the fail position before the FST timeout
Trouble shooting
This error can occur if:
It can be solved by:
Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600
DID-UM-002
Revision: 10
• The valve gets stuck during the test, due to an obstruction in the
hydraulic/pneumatic system
• The valve is moving slow
• Resolve the mechanical problem
• Increasing the FST timeout
vc@valcontrols.com • www.valcontrols.com
51/74