Advertisement

No. 461
FST error: Pressure drop, no breakaway
Description
Breakaway is not detected, but the pressure is below the Minimum breakaway
pressure
Trouble shooting
This error may be due to:
This error can be solved by:
Val Controls A/S • Limfjordsvej 3 • DK-6715 Esbjerg N • Tel. +45 7547 0600
DID-UM-002
Revision: 10
• Actuator is stuck
• Position sensor malfunction
• Check the actuator and valve
• Check the position sensor
• Decreasing the Minimum breakaway pressure
vc@valcontrols.com • www.valcontrols.com