NOTE: Canadian regulations prevent Pace
be wired directly to the power source. Use Canadian Electrical Codes for electrical installation.
115 VOLT 30 AMP CONVERSION (PACE, STRIDE, SX & TX SPAS)
To ensure you will have an opportunity to use your spa soon after delivery, it is very important that the required
electrical service has been installed. Unless otherwise stipulated by your dealer, THIS IS YOUR RESPONSIBILITY.
IMPORTANT: All electrical circuits must be installed by a qualified, licensed electrician.
230 VOLT INSTALLATION (RELAY
STRIDE, SX AND TX CONVERTED SPA MODEL)
Your spa contains a control box designed to operate at 230V, 60Hz. Installation of a 50 amp. dedicated circuit is
required for Relay & Rhythm spas and optional for the other spa models. The control box must be hard wired directly
to a subpanel protected by a Ground Fault Circuit Interrupter (GFCI). The subpanel containing GFCI breakers
is included with the Relay & Rhythm spa models only. Purchase the subpanel from you dealer for the converted
models when converting to 230 volts.
IMPORTANT NOTE: All electrical connections to the control box must be accomplished by a qualified electrician in
accordance with the National Electrical Code and in accordance with any local electrical codes in effect
at the time and place of
installation.
All electrical connections
must be made in
accordance with the wiring
information contained in this
manual and on the back
of the field wiring access
panel of the control box. A
licensed electrician should
install a four-wire electrical
service (two line voltages,
one neutral, one ground)
from the main electrical
service panel to the subpanel.
Your electrician should mount the subpanel in the vicinity of the spa but it should not be closer than five feet (1.5 m)
from the spa water edge (NEC 680-38 to 41-A-3).
INSTALLATION NOTE: After the spa has been installed, your electrician can connect the conduit from the subpanel
to the spa's control box and then complete the wiring connections in the control box. NOTE: Complete step-by-step
Installation and Wiring Instructions for all models are included in the Owner's Manual.
WARNING: Removing or bypassing the GFCI breakers in the subpanel at any time will result in an unsafe spa and
will void the warranty.
x
Pre-Delivery Instructions
Stride, SX spas to come with a power cord and are require to
™,
*
®
230VAC, 50 Amp
2-POLE
CIRCUIT BREAKER
(NON GFCI)
#8 AWG WHITE, NEUTRAL
#8 AWG GREEN, GROUND
#8 AWG BLACK, L1
50A
#8 AWG RED, L2
MAIN SERVICE
ELECTRICAL
PANEL
LESS THAN 100 FT.
230 VAC PERMANENTLY CONNECTED SPA
SEE WIRING
ILLUSTRATION
Page 11
Page 11
Page 11
VERIFY FACTORY JUMPER
REMAINS BETWEEN "N" & "L2"
& RHYTHM
AND OPTIONAL PACE,
®
PERMANENTLY CONNECTED
230 VAC, 50A, 60Hz, MODELS
N
L1
L2
50A
GRD
SUB-PANEL
WITH GFCI
BREAKERS
THE SUB-PANEL MUST BE
WITHIN SIGHT OF THE SPA
NO POWER
JUMPERS REQUIRED
Pre-Delivery Instructions
See
Owner's Manual
for Spa Wiring
*
and Jumper
Configuration
See
Owner's Manual
N, NEUTRAL, #8 AWG WHITE
for Spa Wiring
L2, HOT, #8 AWG RED
and Jumper
L1, HOT, #8 AWG BLACK
GROUND, #8 AWG GREEN*
Configuration
MORE THAN 5 FEET
CONTROL BOX
DO NOT EXCEED 50 FEET
CONVERTED 230VAC SPA MODELS
x