Indoor unit installation
AMS-SVX03A-EN
Wall-mounted unit pipe arrangement sees fi g. (a) and (b) below. Cut off piping blanking at
the main unit base as needed (as shown in fi g. (c)) when arrange left or right pipe (wire).
-
Cut off blanking 1 for leading power wires only.
-
Cut off blanking 1 and 2 (or 1, 2 and 3) for leading connecting pipes and wires
-
,
and
are recommended pipe arrangement.
Packed piping and wire are through the piping hole (as shown in fi g. (d))
Connect the claw at the indoor unit backside with the hanging plate hook. Move the unit to
check stability after installation.
Installation height should not be less than 2.0m.
Right piping
Right rear piping
(a)
Blanking 3
Blanking 2
Blanking 1
(c)
(b)
Connecting pipe
Power supply
wire
(d)
Installation
Left pipi
Left rear piping
Binding ba
Signal con
Drainage p