6.3.1.2 Size 014-040
Shows the fuse size for different combinations of fan sizes and capacity variants. Fan A or B can be a supply air fan or an extract air fan
or vice versa. It is the combination of fan A and B that determines the fuse size.
The air handling unit's rating plate shows the combinations of fan sizes and capacity variants.
Electrical connection is 3-phase, 5-wire, 400 V -10/+15%, 50 Hz.
GOLD PX, size
Fan A, size/capacity variant
014-1 (1,6 kW)
014-1 (1,6 kW)
014-1 (1,6 kW)
014-1 (1,6 kW)
014-2 (2,4 kW)
014/020
014-2 (2,4 kW)
014-2 (2,4 kW)
020-1 (2,4 kW)
020-1 (2,4 kW)
020-2 (3,4 kW)
025-1 (2.4 kW)
025-1 (2.4 kW)
025-1 (2.4 kW)
025-1 (2.4 kW)
025-2 (3.4 kW)
025/030
025-2 (3.4 kW)
025-2 (3.4 kW)
030-1 (4.0 kW)
030-1 (4.0 kW)
030-2 (5.0 kW)
035-1 (4.0 kW)
035
035-2 (5.0 kW)
040-1 (6.5 kW)
040
040-2 (10 kW)
We reserve the right to alter specifications.
Fan B, size/capacity variant
014-1 (1,6 kW)
014-2 (2,4 kW)
020-1 (2,4 kW)
020-2 (3,4 kW)
014-2 (2,4 kW)
020-1 (2,4 kW)
020-2 (3,4 kW)
020-1 (2,4 kW)
020-2 (3,4 kW)
020-2 (3,4 kW)
025-1 (2.4 kW)
025-2 (3.4 kW)
030-1 (4.0 kW)
030-2 (5.0 kW)
025-2 (3.4 kW)
030-1 (4.0 kW)
030-2 (5.0 kW)
030-1 (4.0 kW)
030-2 (5.0 kW)
030-2 (5.0 kW)
035-1 (4.0 kW)
035-2 (5.0 kW)
040-1 (6.5 kW)
040-2 (10 kW)
GB.GOLDSKFPX.210324
Fuse protec-
tion (A)
10
10
10
10
10
10
16
10
10
16
10
16
16
16
16
16
16
16
20
20
16
20
25
40
www.swegon.com
19